Viconics VWZS Integration Guide User Manual
Page 62

62
Object
Index Range Restrictions
Proportional Band-( VT72xx & VT73xx )
1
2 ºF / 1.1 ºC
2
3 ºF / 1.7 ºC
3
4 ºF / 2.2 ºC
4
5 ºF / 2.8 ºC
5
6 ºF / 3.3 ºC
6
7 ºF / 3.9 ºC
7
8 ºF / 4.4 ºC
Pulsed Heat
1
On
2
Off
3
Occupancy Output
RUI1 Config
1
None
2
Filter
3
Service
4
(COC/NH) Change over dry contact.
Normally Heat
5
(COC/NC) Change over dry contact.
Normally Cool
6
(COS) Change over analog sensor
RBI2 Config
1
None
2
Filter
3
Service
Reheat Config
1
None
2
Analogue Duct Heater Only
3
On/Off Duct Heater Only
4
On/Off Peripheral Heating Only
5
Analogue Duct and On/Off Peripheral
Heating
Reheat CPH
1
2 CPH
2
3 CPH
3
4 CPH
4
5 CPH
5
6 CPH
6
7 CPH
7
8 CPH
Zone Sequence
1
Cool
2
Heat
Sequence Of Operation ( VT73xx & VT72xx )
Note 2
1
Cooling only
2
Heating only
3
Cooling & reheat
4
Heating & reheat
5
Cooling & heating 4 pipes
6
Cooling heating 4 pipes & reheat