Viconics VZ7260X Installation Guide User Manual
Page 19

19 | VZ7260W Series- Installation Guide
Channel
Channel selection
Default value = 10
Conditional parameter to Wireless models
(VZ7260CX5x00W) only
This parameter will only appear when a wireless network
adapter is present. If the thermostat is installed with a
BACnet adapter, this parameter will not be used or
displayed
This parameter (Channel) is used to link specific
thermostats to specific Viconics wireless gateway(s)
( VWG / Jace-Driver) or main VZ76 RTU thermostat. For
any system, be sure you set the SAME channel value
both at the network coordinator and all the VZ72
thermostat(s).
Viconics recommends using only the following
channels: 15, 25 & 26
The default value of 10 is NOT a valid channel. The valid
range of available channel is from 11 to 26
Range is: 10 to 26
ZoneBaud
Zone Thermostat
Communication Baud Rate
Default Value: 4 = Auto
Conditional parameter to BACnet MS-TP models
(VZ7260CX5x00B) only
This parameter will set the network’s baud rate.
0 = 9600 KBps
1 = 19200 KBps
2 = 38400 KBps
3 = 76800 KBps
4 = Auto Bauding ( Baud Rate will match detected Baud
Rate