Viconics VZ7656F Wireless Installation Guide User Manual
Page 20

20 | VZ7656F1000W Installation Guide
Channel
Channel selection
Default value = 10
Range is: 10 to 26
This parameter (Channel) is used to link specific
controllers to specific Viconics wireless gateway(s) (VWG
/ Jace-Driver) or to the main VZ76xx RTU controller. For
any system, be sure you set the SAME channel value
both at the network coordinator and on all the VZ72xx
controller(s).
Viconics recommends using only the following channels:
15, 25 & 26.
The default value of 10 is NOT a valid channel. The valid
range of available channels range from 11 to 26.
Lockout Keypad lockout levels
Default value = 0 No lock
0 = No lock
1 = Low level
2 = High level
USER KEY FUNCTIONS
LEVEL
Global
Unocc.
Override
System mode
setting
Schedules
setting
Clock setting
0
1
2
pwr del
Power-up delay
Default value = 10 seconds
On initial power up of the Terminal Equipment Controller
(each time 24 VAC power supply is removed & re-applied)
there is a delay before any operation is authorized (fan,
cooling or heating). This can be used to sequence start up
multiple units / Terminal Equipment Controller in one
location.
10 to 120 seconds