VZ7260 List of Property Enumeration Sets for MV Objects
Object Name
Object
Type and
instance
BACnet Index
Text
Default value
Cfg Zone Baud
MV 1
1
9600 ( Bps )
Auto
2
19200 ( Bps )
3
38400 ( Bps )
4
76800 ( Bps )
5
Auto
Cfg Reheat
Configuration
MV 2
1
None
None
2
Analog Duct Heater
Only
3
On/Off Duct Heater
Only
4
On/Off Perimeter
Heater Only
5
Analog Duct Heater
with On/Off Perimeter
Heater
Cfg BI1
Configuration
MV 3
1
None
None
2
Motion NO
3
Motion NC
Cfg PI Heat Weight
MV 4
1
0 %
100 %
2
25 %
3
50 %
4
75 %
5
100 %
Cfg PI Cool Weight
MV 5
1
0 %
100 %
2
25 %
3
50 %
4
75 %
5
100 %
Cfg Temporary
Occupancy Time
MV 6
1
0 hour
2 hours
2
1 hour
3
2 hours
4
3 hours
5
4 hours
6
5 hours
7
6 hours
8
7 hours
9
8 hours
10
9 hours
11
10 hours
12
11 hours
13
12 hours