18 | VZ7260B Series - Installation Guide
BI1
Binary input no.1
configuration
Default: None
(None): No function will be associated with the input. Point
can still be monitored through the BACnet ™ network.
(Motion NO): Used in Occupied Mode only to toggle from
the Occupied setpoints to the Stand-By setpoints when no
motion is detected for 60 minutes at the zone.
When motion is detected at the zone, the Occupied
setpoint resumes.
Contact opened = No motion detected.
Contact closed = Motion detected.
(Motion NC): Used in Occupied Mode only to toggle from
the Occupied setpoints to the Stand-By setpoints when no
motion is detected for 60 minutes at the zone.
When motion is detected at the zone, the Occupied
setpoint resumes.
Contact opened = Motion detected.
Contact closed = No motion detected.
AI4
Analog input no.4
configuration
Default: None
(None): No function will be associated with the input. Point
can still be monitored through the BACnet network.
CO2: Used when a 0-10VDC CO2 sensor is connected to
AI4 input. The value of the input signal is displayed in AI4
Dis parameter.