Viconics VWG-50 (Classic ZigBee) Design Consideration and Setup Guide User Manual
Page 28

28 | VWG-50-Setup Guide
BACnet Points Viewer
This shows all the of the point objects that are loaded on the VWG BACnet export table
from each controller
BACnet points include:
Analog Values
Binary Values
Multistate Values
The displayed BACnet object names are displayed as configured by the installer from the
general parameters section, under point name convention.
To view only the objects from any specific controller; in the “Controller Manager” tab,
double click on the
icon.
IMPORTANT NOTES (Please Read Carefully):
For every controller reporting to a gateway (maximum of 50 controllers per
gateway), be sure you set the SAME PAN ID and Channel value at both the
gateway and the controller(s).
When properly configured, the issue of RF interference and lost data between
the gateway and the controllers can be avoided. Without proper care or proper
software configuration serious interference issues can happen.
Viconics
highly recommends the use of 802.15.4 channels 15 & 25 only.
802.11 Wi-Fi transmissions overlap and “may” interfere with other channel
selection allowed by 802.15.4 (Channels 11 to 14 & 16 to 24)