C1012 electronic thermostat

Advertising
background image

HOW TO ORDER

Thermostat

C1010-02

C1011-02 **

C1012-02

C1013-02 **

Tri-state output in cooling mode

z

z

z

z

Tri-state output reverses to heating mode

with change over sensor

z

z

Auxiliary reheat

1 stage

1 stage

** these packages include the auto change over sensor.

C1012

Electronic Thermostat

APPLICATIONS

• VAV and by-pass units control

with modulating tri-

state floating output

Single stage of auxiliary reheat

ADVANCED DESIGN AND PI CONTROL

Advanced PI control thermostats provides precise
temperature control and eliminates wasted energy caused
by the typical On / Off cycling in conventional thermostats.
Thus the room occupant is able to reduce the thermostat
setpoint to the lowest comfortable setting. The result is
energy savings ranging from 5% to 10%.

DIMENSIONS

50

90

80

70

60

F

114 mm

32 mm

( 71 mm )

( 71 mm )

2.8"

2.8"

4.5"

1.275"

5

4

3

2

1

7

6

( 83 mm )

3.275"

SECURITY SCREW

FROM BACK

WIRING

BASE

( 71 mm )

2.8"

SCREW TERMINALS

COVER TOP

COVER INSIDE

MODULATING TRI-STATE FLOATING OUTPUT

For use with tri-state floating actuator (CW/Off/CCW)
having a 1 to 2 minutes timing per 90° of rotation. This is
a true multi positions modulating output. It gives
performances which is equivalent to more expensive 0 to
10 Vdc type output.

SINGLE STAGE OF AUXILIARY REHEAT

To be used with On/Off 2 position 24 Vac devices like:
• On/Off N.C. electric valves
• Electric duct heater relays
• Electric base board relays

See and study wiring diagrams carefully to wire reheat
devices using a separate power source.

COVERS

Factory standard scale is 10°C to 32°C for horizontal
mounting. °F & °C scales are available on special order
for horizontal or vertical mounting. The thermostat and the
terminals are an integral part of the cover. The cover
hooks onto the base for easy service and is locked in
place using a security screw.

SPECIFICATIONS

Operating

Conditions:

0 °C to 50 °C ( 32 °F to 122 °F )

0% to 95% R.H. non-condensing

Sensor:

Local 47 K NTC thermistor

Resolution:

± 0.1 °C ( ± 0.2 °F )

Control accuracy

(calibrated):

± 0.2 ° C ( ± 0.4 °F )

Ranges:

50 °F to 90 °F Standard
( 10 °C to 32 °C ) Optional

Outputs:

Isolated Triac: 30 Vac at ½ A max.

Power:

24 VAC -15%, +10% 50/60 Hz; 2 VA

Specifications and equipment are subject to change without prior
notice.