Dip switch adjustment per applications, Control curves and sequence typical applications – Viconics C1110 User Manual

Page 2

Advertising
background image

Viconics Electronics Inc. 9245, Langelier Blvd, St-Leonard, Quebec, Canada H1P 3K9

www.viconics.com

[email protected]

LIT-C1110-E01

DIP SWITCH ADJUSTMENT PER APPLICATIONS

S3

APPLICATION SWITCH

0

Direct acting control signal

1

Reverse acting control signal

CONTROL CURVES AND SEQUENCE

TYPICAL APPLICATIONS

Room Temperature Control With:

Analog 0 to 10 Vdc Valve Actuators

Dip switch position

S3

Direct acting control signal

0

Reverse acting control signal

1

50 %

100%

0%

Temperature increase

10 Vdc

DIAL SETPOINT

S3 = 0

Direct acting

S3 = 1

Reverse acting

0 Vdc

Perimeter Heating Valve

Room Temperature
Control Thermostat

50

70

60

90

80

F

Analog Cooling Or Heating Valve

Room Temperature
Control Thermostat

50

70

60

90

80

F

Common

24 Vac

0 to 10 Vdc

3
4

0 to 10

Vdc

5