DIP SWITCH ADJUSTMENT PER APPLICATIONS
S3
APPLICATION SWITCH
0
Direct acting control signal
1
Reverse acting control signal
CONTROL CURVES AND SEQUENCE
TYPICAL APPLICATIONS
Room Temperature Control With:
Analog 0 to 10 Vdc Valve Actuators
Dip switch position
S3
Direct acting control signal
0
Reverse acting control signal
1
50 %
100%
0%
Temperature increase
10 Vdc
DIAL SETPOINT
S3 = 0
Direct acting
S3 = 1
Reverse acting
0 Vdc
Perimeter Heating Valve
Room Temperature
Control Thermostat
50
70
60
90
80
F
Analog Cooling Or Heating Valve
Room Temperature
Control Thermostat
50
70
60
90
80
F
Common
24 Vac
0 to 10 Vdc
3
4
0 to 10
Vdc
5