SEQUENCE OF OPERATION

When 24 Vac is applied to the thermostat, the minimum voltage output going to the actuator is 0 Vdc, or the value adjusted on
the minimal position potentiometer.

When the dry contact closes on the supply sensor wire, the free cooling mode is activated.

The setpoint is adjusted on the thermostat, the range of the setpoint is: 5 °C to 27 °C ( 40 °F to 80 °F ). The voltage output going
to the actuator when the free cooling is activated is the highest value between the PI supply loop or the minimum position
adjustment.

To close the damper two choices are available. Remove power to the thermostat and the control signal will drop to 0 Vdc, this
will close the actuator electrically. Or remove the power to the thermostat and the actuator, this will close the actuator on its
spring mechanism if it is equipped with one.

Sensor and thermostat are made to be operated at temperature as low as -40 °C ( -40 °F ).


WIRING

24 V.a.c.

M18

2 to 10 Vdc

actuator

Ex.: NF24-SR

22-003

Supply

N.O.

N.C.

Mix air setpoint

Fresh air damper

minimum

position

Contact from a relay

authorizing free cooling

Air

Return

Fan

7

6

5

4

1

2

3

24 V.a.c.

Common

Remote

sensor

Output

0 - 10 Vdc

Order

sensor

separately

Air

Fresh

Optionnal contact from a

relay overrides the fresh air

damper to 100%

www.viconics.com