Locating stove continued, Minimum clearances to combustible surfaces – Vogelzang BX22EL User Manual

Page 7

Advertising
background image

VGZ-003 / 20120224.1

BX22EL /

Page 7

Figure 9 – Top View

Minimum Corner Clearances from

Combustible Surfaces

30"/76.2cm

CORNER CLEARANCES

30"/76.2cm

LOCATING STOVE continued…

COMBUSTIBLE

CONSTRUCTION IN

ACCORDANCE WITH

NFPA 211

FLOOR

PROTECTOR

DASHED LINE SHOWS

HORIZONTAL CHIMNEY

CONNECTOR AND

ADDITIONAL FLOOR

PROTECTION REQUIRED

BACKWALL

27"/68.6cm

(TOP VIEW)

8"/21cm

8"/21cm

8"/21cm

32"/81.3cm

36"/91.4cm

51"/129.6cm

18"/46cm

SIDEWALL

COMBUSTIBLE

CONSTRUCTION IN

ACCORDANCE WITH

NFPA 211

34.5"/87.6cm

Figure 7 – Minimum Clearance Dimensions

from Combustible Surfaces

Figure 8 – Top View Minimum Clearance

Dimensions from Combustible Surfaces

CAUTION: KEEP FURNISHINGS AND OTHER
COMBUSTIBLE MATERIALS AWAY FROM THE
STOVE.

MINIMUM CLEARANCES

TO COMBUSTIBLE SURFACES

Unit to Sidewall ...............................................36˝ / 91.4cm
Unit to Backwall ..............................................32˝ / 81.3cm
Unit Corner to Wall ..........................................30˝ / 76.2cm
Pipe Connector to Backwall ........................34.5˝ / 87.6cm
Pipe Connector to Ceiling ...............................18˝ / 45.7cm

9. This stove meets Test Standards: UL 1482-2011

and Canadian Standard: ULC-S627-00.

Failure to follow these minimum clearance re-
quirements may result in an unsafe installation
and could cause a fire.

CAUTION: KEEP FURNISHINGS AND OTHER
COMBUSTIBLE MATERIALS AWAY FROM THE
STOVE.

WARNING: DO NOT USE SINGLE WALL CON-
NECTOR PIPE AS A CHIMNEY - A HOUSE FIRE
COULD RESULT.