Locating stove …continued – Vogelzang TR003 User Manual
Page 5

VGZ-028 / 20120208.0
TR003X HIGHLANDER™ /
Page 5
CAUTION: KEEP FURNISHINGS AND OTHER
COMBUSTIBLE MATERIALS AWAY FORM THE
STOVE AND OUTSIDE MINIMUM CLEARANCES.
CAUTION: REPLACE FIREBRICKS BEFORE
FIRING WOODSTOVE. POSITION FIREBRICKS
SO NO GAPS REMAIN BETWEEN BRICKS.
LOCATING STOVE …continued
Fig. 1 – TOP VIEW Minimum Clearance Dimensions from Combustible Surfaces
FLOOR
PROTECTOR
DASHED LINES SHOW HORIZONTAL CHIMNEY CONNECTOR
AND ADDITIONAL FLOOR PROTECTOR REQUIRED BENEATH
AND EXTENDING 2” BEYOND EACH SIDE
COMBUSTIBLE CONSTRUCTION IN ACCORDANCE WITH NFPA 211
BACKWALL
SIDEWALL
12"min.
17"
45"
16"min.
6"min.
25.5"
15"
min.
12"min
TOP VIEW
37.5"
2. The stove must have its own flue.
DO NOT
CONNECT THIS UNIT TO A CHIMNEY FLUE
SERVING OTHER APPLIANCES.
3. After observing the clearances to combus-
tible materials (figures 1–3), locate your floor
protector accordingly (figure 1) and careful-
ly place the stove in your selected location.
Install stove pipe, elbows, and thimble as
required, utilizing either a recently cleaned and
inspected 6” masonry chimney or a 6” i.d. listed
chimney.
4. U s e 6 ” r o u n d b l a c k s t o v e p i p e , n o t
galvanized stove pipe. Secure pipe sections with
three (3) sheet metal screws in each stove pipe
and/or elbow joint to firmly hold the pipe sections
together. Do Not connect this stove to any air dis-
tribution or duct system.
5. Recheck clearances from the stove, con-
nector stove pipe, and cor ner clearanc-
es using the illustrations in figures 1–3 and
your local building codes or fire protection
ordinances.
NOTE: Drywall faced with brick or stone must
be considered a combustible surface.
6.
D O N O T I N S TA L L T H I S S T O V E I N A M O -
BILE HOME, MANUFACTURED HOME, TRAIL-
ER OR TENT
– NO EXCEPTIONS! (HUD Federal
Standard: 24 CFR Ch.XX)
Continued on next page
7. T h e c l e a ra n c e s p r ov i d e d a r e m i n i mu m
dimensions determined by Omni Test Lab-
oratories, Inc., the manufacturer’s testing
laboratory. Installation of this stove must
comply with the latest edition of NFPA 211 for
reduced clearances and/or your local build-
ing code rulings. Use whichever minimum
dimensions are LARGEST.
Failure to follow these minimum clear-
ance requirements may result in an unsafe
installation and could cause a fire.
8. T h i s s t ove m e e t s U. S. Te s t S t a n d a r d :
UL 1482-1996.
9. Always locate stove to provide a source of fresh
air into the room where the unit is installed.
Failure to do so may result in air starvation of other
fuel burning appliances and the possible develop-
ment of hazardous conditions.