Vogelzang TR007 User Manual

Page 6

Advertising
background image

Page 6 / TR007 PONDEROSA™

Vogelzang International Corp.

VGZ-031 / 20120619.1

1. The stove must be placed on solid concrete, solid

masonry, or when installed on a combustible floor,
on an Underwriters Laboratories Listed Type 2 floor
protector listed to UL standard UL 1618, such as
Hy-C or Imperial Model UL4056BK. Floor protector
must be 1/2˝/13mm minimum thickness (R value
= 1.19, K value = 0.84
see page 23 for calculation
formulas) non-combustible material or equivalent.
The floor protector must extend at least 18˝/46cm
beyond the front of the access door, 8˝/21cm to
the sides, 8˝/21cm beyond the rear and must
extend under and 2˝/50mm beyond either side of
the stove pipe if it is elbowed towards a wall. (See
figures 4 – 6 and consult local building codes and
fire protection ordinances.)

CAUTION: FIRE HAZARD. CARPETING AND
OTHER COMBUSTIBLE MATERIAL SHALL
NOT COVER THE FLOOR PROTECTOR. THESE
MATERIALS MUST REMAIN OUTSIDE OF COM-
BUSTIBLE CLEARANCES, SEE FIG. 5 – 7

2. The room in which the stove is installed must have

a minimum floor to ceiling height of 8 ft. (2.4 m).

3. The stove must have its own flue. Do not con-

nect this unit to a chimney flue serving other
appliances.

DO NOT CONNECT TO ANY AIR

DISTRIBUTION DUCT OR SYSTEM.

4. After observing the clearances to combus-

tible materials (figures 4 – 6), locate your floor
protector accordingly (figure 4) and careful-
ly place the stove in your selected location.
Install connector pipe, elbows, and thimble as
required, utilizing either a recently cleaned and
inspected 6˝/152mm lined masonry chimney or a
6˝/152mm i.d. manufactured chimney system listed
to UL 103 HT (US)/ULC-S629 (CDN).

5. Use round 6˝/152mm dia., minimum 24 MSG black

or 26 MSG blue steel stove pipe to connect the
stove to the chimney. Do not use galvanized stove
pipe.

NOTE: Mobile home installations require

double-wall UL 103 HT high-temp connector
pipe.
Secure connector pipe to the flue collar with
three (3) equally spaced sheet metal screws to

firmly hold the pipe sections together. DO NOT
CONNECT THIS STOVE TO ANY AIR DISTRIBU-
TION OR DUCT SYSTEM.

6. Recheck clearances from the stove, con-

nector stove pipe, and cor ner clearanc-
es using the illustrations in figures 4 – 6 and
your local building codes or fire protection
ordinances.

NOTE: ANY WALL CONTAINING COMBUSTI-
BLE MATERIAL SUCH AS WOODEN STUDS OR
DRYWALL AND FACED WITH BRICK OR STONE
MUST BE CONSIDERED A COMBUSTIBLE
SURFACE.

7.

NOTICE: for installation in a manufactured/
mobile home (USA only), please see specific
requirements on page 10.

8. The clearances provided are minimum

dimensions set by US standard UL 1482-2011 &
ULC-S627-00, tested and applied by OMNI-Test
Laboratories, Inc. the manufacturer’s test-
ing agency. Installation of this stove must
comply with the latest edition of NFPA 211
(US)/CAN/CSA-B365 (CDN) for reduced
clearances and/or your local building code
rulings. Use whichever minimum dimensions are
LARGEST.

Clearances listed and shown MUST be adhered to
for safe operation of this appliance.

CLEARANCES

MAY NOT BE REDUCED BY ANY MEANS IN USA
OR CANADA
.

9. This stove meets U.S. Test Standard: UL 1482-

2011& Canadian Standard: ULC-S627-00.

CAUTION: KEEP FURNISHINGS AND OTHER
COMBUSTIBLE MATERIALS AWAY FROM THE
STOVE.

NOTE: BEFORE FIRING WOODSTOVE SLIDE
FIREBRICKS TOWARDS THE REAR SO NO
GAPS REMAIN BETWEEN BRICKS.

aligning the fan opening to the opening in the back
of the stove. Secure with four sheet metal screws.

4. After assembly, check to make sure fire brick are

properly positioned and ash clean out cover is in
place.

ASSEMBLY INSTRUCTIONS . . . continued

LOCATING STOVE

5. Route the power cord away from stove. Do not

allow the power cord to touch any hot surfaces.
Keep power cord at least 12˝ from stove surfaces.

6. Once stove is positioned, plug power cord into a

grounded 120v outlet.

Advertising