Locating stove continued – Vogelzang TR008 User Manual

Page 7

Advertising
background image

TR008-96 | 20120425.0

www.vogelzang.com

DURANGO™

| Page 7

FLOOR

PROTECTOR

DASHED LINES SHOW HORIZONTAL CHIMNEY CONNECTOR

AND ADDITIONAL FLOOR PROTECTOR REQUIRED BENEATH

AND EXTENDING 2” BEYOND EACH SIDE

COMBUSTIBLE CONSTRUCTION PER NFPA 211

BACKWALL

SIDEWALL

31"

4 8"

16"min.

6"min.

17"

22"

min.

25.8"

min.

14"

min.

11"

min.

TOP VIEW

29"

TR008

CAUTION: FAILURE TO FOLLOw ThESE
M I N I M U M C L E A R A N C E R E q U I R E -
MENTS MAY RESULT IN AN UNSAFE
INSTALLATION AND COULD CAUSE A FIRE.

8. T h i s s t ove m e e t s U. S. Te s t S t a n d a r d :

UL 1482-1996.

9. Always locate stove to provide a source of fresh

air into the room where the unit is installed.
Failure to do so may result in air starvation of other
fuel burning appliances and the possible develop-
ment of hazardous conditions.

NOTE: ANY wALL CONTAININg COMBUSTI-
BLE MATERIAL SUCh AS wOODEN STUDS OR
DRYwALL AND FACED wITh BRICk OR STONE
MUST BE CONSIDERED A COMBUSTIBLE
SURFACE.

6. DO NOT INSTALL ThIS STOVE IN A MOBILE

hOME, MANUFACTURED hOME, TRAILER OR
TENT – NO EXCEPTIONS! (HUD FEDERAl
STANDARD: 24 CFR CH.xx)

7. T h e c l e a ra n c e s p r ov i d e d a r e m i n i mu m

dimensions determined by OMNI-Test Lab-
oratories, Inc., the manufacturer’s testing
laboratory. Installation of this stove must
comply with the latest edition of NFPA 211 for
reduced clearances and/or your local build-
ing code rulings. Use whichever minimum
dimensions are LARGEST.

Fig. 5 – Top View minimum Clearance Dimensions from

Combustible Surfaces

13"

19"

19"

13"

CORNER CLEARANCES

Fig. 6 – minimum Corner Clearance

Dimension from Combustible Surfaces

Fig. 7 – Front & Side Views: Minimum Clearance Dimensions

from Combustible Surfaces

CAUTION: kEEP FURNIShINgS AND
OThER COMBUSTIBLE MATERIALS
AwAY FORM ThE STOVE AND OUTSIDE
MINIMUM CLEARANCES.

lOCATING STOVE continued…