FIGURE 7

TYPICAL THROUGH THE WALL INSTALLATION

THROUGH THE WALL INSTALLATION

(RECOMMENDED INSTALLATION)

Canadian installations must conform to CAN/CSA-B365.
To vent the unit through the wall, connect the pipe adapter
to the exhaust motor adapter. If the exhaust adapter is at
least 24 in.(609mm) above ground level, a straight section
of pellet vent pipe can be used through the wall.
Your heater dealer should be able to provide you with
a kit that will handle most of this installation, which will

include a wall thimble that will allow the proper clearance
through a combustible wall. Once outside the structure,
a 3 in.(76mm) clearance should be maintained from the
outside wall and a clean out tee should be placed on the
pipe with a 90-degree turn away from the house.

The Clean

out tee must be placed at the bottom of the vertical section
of venting, NOT in the horizontal section.

At this point, a 3ft

(0.91m) (minimum) section of pipe should be added with
a horizontal cap, which would complete the installation
(see FIGURE 7).
A support bracket should be placed just below the
termination cap or one every 4ft (1.22m) to make the
system more stable. If you live in an area that has heavy
snowfall, it is recommended that the installation be taller
than 3ft (0.91m) to get above the snowdrift line. This same
installation can be used if your heater is below ground level
by simply adding the clean-out section and vertical pipe
inside until ground level is reached. With this installation
you have to be aware of the snowdrift line, dead grass, and
leaves. We recommend a 3ft (0.91m) minimum vertical
rise on the inside or outside of the house.

The “through the wall” installation is the least expensive and simplest installation. Never terminate the vent under a
deck, in an alcove, under a window, or between two windows. We recommend Simpson Dura-Vent

®

or Metal-Fab

®

kits.

THROUGH THE ROOF/CEILING INSTALLATION

When venting the heater through the ceiling, the pipe is connected the same as through the wall, except the clean-out
tee is always on the inside of the house, and a

3 in.(76mm)

adapter is added before the clean-out tee. The Clean out

tee must be placed at the bottom of the vertical section of venting, NOT in the horizontal section.
You must use the proper ceiling support fl anges and roof fl ashing (supplied by the pipe manufacturer; follow the pipe
manufacturer’s directions). It is important to note that if your vertical run of pipe is more than 12ft (3.7m), the pellet vent
pipe size should be increased to 4 in. (102mm) in diameter coming from the back of the stove.
Do not exceed more than 4

ft (1.22m)

of pipe on a horizontal run and use as few elbows as possible. If an offset is

required, it is better to install 45-degree elbows rather than 90-degree elbows.