Winco 2-Wire Conversion Instructions PSS15B User Manual

Page 2

Advertising
background image

225 SOUTH CORDOVA AVE
LE CENTER MN 56057
Phone: 507-357-6831
www.wincogen.com

8.

Reconnect the two black connectors; be sure to turn the locking rings on tight. But do not

over tighten or you will break the locking rings.

9.

Locate the small white 2 wire connector on the back end of the unit tie wrapped to the AC

harness running from the generator to the customer control box. This connector must be
plugged into the mating connector on the side of the new engine control. (This is a 120-Volt
signal for the stop crank relay inside the engine control. If it is not connected the starter will
never disengage and the unit will go into fault.)

10. Inside the DC portion of the customer connection box locate wire #22. Using the wire tag
#23 provided in the kit relabel wire #22 to #23.

11. Cover the 4-wire decal # 64576-011 on the backside of the customer connection box cover
with the 2-wire decal 64576-015. This is the new wiring instruction for connecting the unit to an
Automatic Transfer Switch. See New operators manual for addition wiring details.

12. Reinstall the cover on the connection box.

13. Locate the engine control description label just to the left of the engine control. A new label
has been provided with this kit, paste it over the existing label.

14. Remove the operators manual part number 60706-185 for model PSS15B4W from the
literature package and replace it with operators manual part number 60706-186 for Model
PSS15B2W. This replacement manual contain the proper information for installation and
operation of a 2-wire auto start system. The customer must have this manual in order to start
and operate the unit after the installation of the new engine control.

15 Reconnect the Negative battery cable if the battery is installed. Be sure the toggle switch
on the engine control is in the OFF position.

16. Replace the end panel.

17. Install the label “THIS UNIT HAS BEEN CONVERTED TO USE A TWO-WIRE START
ENGINE CONTROL” just below the engine control inside the enclosure.

18. Using the new operators manual, 60706-186 this unit is know ready to be installed as a
standard 2-wire start system. This Generator set will now work with any transfer switch that
provides a ‘dry’ relay closure for a start/run signal

If you encounter any problems or need assistance,
feel free to contact the WINCO Service Department
at 507-357-6831