Preventive maintenance – Winco PSS10H/A User Manual

Page 13

Advertising
background image

PAGE 11

2234-01

60706-152

switch.

5.

Defective start/stop relay in ATS.

ATS PANEL WILL NOT PULL IN ON
NORMAL POWER.

1.

Proper normal line power not available at line
terminals in ATS panel.

2.

Defective holding coil in line side contactor.

3.

Broken or defective mechanical/electrical inter-
lock.

4.

Defective start/stop relay in ATS.

NO AC OUTPUT FROM GENERATOR.

1.

Diodes on rotor blown.

2.

Defective capacitor(s).

3.

Defective rotor.

4.

Defective stator.

5.

AC short in the output leads.

6.

Unit has lost its residual voltage.

7.

Rotor loose on engine crankshaft.

8.

Low engine speed, must be 3600 RPM.

9.

AC short on output leads.

PREVENTIVE MAINTENANCE

Reasonable care in preventive maintenance will insure

high reliability and a long life for the engine generator set
and the Automatic Transfer Switch.

*************
***** WARNING ****
*************
When performing any type of maintenance on this
equipment make sure the selector switch on the engine
generator is in the off position. If you are working in the
Automatic Transfer Switch, confirm with a reliable meter
that all power has been disconnected.

AUTOMATIC TRANSFER SWITCH

Clean and inspect the switch once a year. De-energize

all power sources, both line and engine generator set,
then brush and vacuum away any excessive dust and
dirty accumulation. You can at this time with the contactor
de-energized remove the contactor covers and check the
contacts. Make sure the contacts are clean and not
burned or pitted.

ENGINE GENERATOR SET

Service the engine in accordance with the engine

manufacturers manual provided with your new equip-
ment. Routinely remove debris and dirt from around and
inside generator enclosure. Insure that the air intakes
are free from leaves and other debris at all times.

Clean and inspect battery terminals at least twice a

year. Check the battery water level at least twice a year
also.

Other than keeping the generator clean and free of

debris there is no other routine or preventive mainte-
nance required, as long as the generator is run once a
week to keep it dry and in good working order.