TESTING POLICY:

Before any generator is shipped from the factory, it is fully
checked for performance. The generator is loaded to its full
capacity, and the voltage, current, and frequency are carefully
checked.

Rated output of generators is based on engineering tests of
typical units, and is subject to, and limited by, the temperature,
altitude, fuel, and other conditions specified by the manufacturer
of the applicable engines.

INTRODUCTION AND DESCRIPTION

The package standby engine generator set includes all items
necessary for a completely automatic standby power system as
standard equipment. The entire package is then tested to
insure proper operation of all components and the total system
performance and reliability.

DESCRIPTION

This package power system is designed to automatically provide
standby power to unattended loads during electrical outages.
Upon an interruption of normal electrical service this package
power systems electrical control circuits will automatically start
the engine. The generator will produce electrical power and the
Automatic Transfer Switch (A.T.S.) will automatically transfer the
electrical loads to the engine-generator set. Upon restoration of
normal electrical service the A.T.S. will sense return of the normal
commercial power and retransfer the load back to normal
commercial power source. The engine control circuits will begin a
3 minute cool-down cycle, after which the fuel supply will be shut
off and the engine ignition system disabled.

These package power systems consist of two major components:

1) WINCO AUTOMATIC TRANSFER SWITCH

(Non-UL model)

The table below shows the different Automatic Switch sizes
typically used with each unit.

CONTACTOR RATING

MODEL

VOLTAGE

LINE

GENERATOR

PSS50LS-3

120/240

230

230

PSS50LS-4

120/208

230

230

PSS50LS-17

120/240

230

230

PSS50LS-18

277/480

*

*

PSS75LS-3

120/240

400

320

PSS75LS-4

120/208

400

320

PSS75LS-17

120/240

400

320

PSS75LS-18

277/480

*

*

*Special order UL Transfer Switches

These Automatic Transfer Switches (A.T.S.) are wall mount
switches designed for inside installation. The A.T.S. consists of
a line side contactor and a generator side contactor. The
contactors are both electrically and mechanically interlocked. A
seven day electronic exerciser clock is installed in the A.T.S. as
standard equipment. The A.T.S. also contains the power failure
sensing circuitry necessary to send a start/stop signal to the
engine generator set.

2) ENGINE/GENERATOR

PSS50LS- The engine generator set consists of a GM 5.7L V-8
industrial, liquid cooled engine equipped to run on L.P./N.G. fuel.
The engine operates at 1800 rpm and frequency regulation is
maintained by the electronic governor within .5 cycles variation,
from no load to rated load. The 50,000 watt (50kW) generator is
a single bearing, direct drive, rotating field design. The generator
is connected to the engine flywheel via flexible drive disks. The
engine generator is mounted in a drip proof enclosure for outside
installation. Connection boxes are provided to all customer
connections (both AC output and DC control). A customer
supplied
12 Volt, 650 CCA (BCI group 24) battery is required to
complete the installation. Engine operation is controlled by an
Digital Genset Controller (DGC) mounted in the engine generator
enclosure.

PSS75LS - The engine generator set consists of a GM 5.7L ,
Turbo charged V-8 iIndustrial, liquid cooled engine equipped to
run on L.P./N.G. fuel. The engine operates at 1800 rpm and
frequency regulation is maintained by the engine governor within
.5 cycles variation, no load to rated load. The 75,000 watt (75kW)
generator is a single bearing, direct drive, rotating field design.
The generator is connected to the engine flywheel via flexible
drive disks. The engine generator is mounted in a drip proof
enclosure for outside installation. Connection boxes are provided
to all customer connections (both AC output and DC control). A
customer supplied 12 Volt, 650 CCA (BCI group 24) battery is
required to complete the installation. Engine operation is con-
trolled by an Digital Genset Controller (DGC) mounted in the
engine generator enclosure.

** NOTICE **

These units will automatically transfer if a power outage occurs
while running in an exercise mode.

Digital Genset Controller

The Digital Genset Controller (DGC) is a programmable engine
control module utilizing the latest technology in digital control.
The DCGs in these units have been programmed to meet the
more sophisticated needs of today's generator users.

The following system settings have been programmed into the
DCG:

Start Delay

10 Seconds

Generator Cranking Style

Cycle

Number of Cranking Cycles

3

Cycle Crank Duration

15 Seconds

Crank Disconnect

30% of Rated Speed

Cool Down Timer

5 Minutes

High Coolant Lockout

60 Seconds

Low Oil Pressure Delay

10 Seconds

The following pre-alarm and alarm setting have been pro-
grammed in the DCG:

Pre-Alarm

Alarm

High Coolant Temp (Deg F)

210

230

Low Oil Pressure

25 PSI

15 PSI

Overspeed

N/A

115%