Description, Unpacking, Specifications – Winco W165PTOT User Manual

Page 4: Assembly

Advertising
background image

Page 2

60706-160 REV 3

3117-30

DESCRIPTION

The WINCO PTO drive generator will provide, depending on
the unit purchased, 120/240V single phase, 120/240V three
phase, 120/208 three phase or 277/480 three phase 60Hz
electrical service when direct-driven. Tractor or vehicle power
take-off shafts, can be used for driving these generators.

NOTE: The prime mover which drives the generator must be
capable of delivering approximately 2 HP per 1000 watts
output from the generator. Observe input RPM specifications.

The generator may be foundation mounted for use as standby
power source, or trailer mounted, and used as portable
electrical power sources for areas where commercial power
is not readily available, such as out buildings.

This generator includes an Automatic Voltage Regulator (AVR)
which maintains a constant voltage output and a Frequency
meter to insure the unit is producing 60 Hz power. All the
models (except the 480 volt units) have a control panel with
two output power receptacles, and overload protection circuit
breakers, and most models are equipped with a full load
disconnect plug (not applicable on the 135, 145 and 150 kW
models) To reduce maintenance problems, the coupling
between the generator input shaft and rotor consists of
precision helical gearing. The input shaft is 1-3/4 in diameter
20 spline .

The factory thoroughly tests each of these generators before
shipment. All are continuous duty rated.

IMPORTANT: THE MANUFACTURER STRONGLY RECOM-
MENDS RUNNING THE GENERATOR UNDER LOAD AT
LEAST ONCE A MONTH IN ORDER TO EVAPORATE ANY
ACCUMULATED MOISTURE CONDENSATION

UNPACKING

CAUTION: Equipment Damage

DO NOT invert generator during unpacking. The Gearcase
contains oil which will leak out if inverted during unpacking.

Unpack the generator as follows:

1. Remove the crate.

2. Examine the unit for damage.

3. Find the small subpack carton packed in the large carton.
Be careful not to throw away the subpack carton with the large
carton.

4. Open the subpack carton and make sure it contains:

a. Generator instruction manual

b. Load disconnect plug (disassembled, in bag)

5. Remove the four bolts which hold down the generator feet
to the pallet.

6. Lift the generator from the pallet by means of the lifting eye
on the top of the generator.

7. Inspect the generator carefully for freight loss or damage. If
loss or damage is noted at time of delivery, require that the

person making the delivery make note of the loss or damage
on the freight bill, or sign the consignee’s memo of the loss or
damage. Contact the carrier for claim procedures.

When loss or damage is noted after delivery, segregate the
damaged material, and contact the carrier for claim proce-
dures.

“Concealed damage” means damage to the contents of a
package which is not evident when the package is delivered
by the carrier, but which is discovered later. The carrier or
carriers are responsible for merchandise lost or damaged in
transit. The title to the goods rests with the consignee when
the goods are shipped FOB factory, and only the consignee
can legally file claims.

Specifications

MODEL

VOLTAGE

PHASE

P/F

AMPERAGE

W85PTOS

120/240

Single

1.0

354

W100PTOS

120/240

Single

1.0

416

W105PTOT-4

120/208

Three

0.8

365

W105PTOT-17

120/240

Three

0.8

316

W105PTOT-18

277/480

Three

0.8

158

W135PTOS

120/240

Single

1.0

560

W145PTOT-4

120/208

Three

0.8

504

W145PTOT-17

120/240

Three

0.8

436

W165PTOT-18

277/480

Three

0.8

198

W150PTOS

120/240

Single

1.0

625

Assembly

The only assembly work required after unpacking the genera-
tor is to assemble the load disconnect plug, which is con-
tained in a bag in the subpack carton packed in the generator
crate. NOTE - The 135kW, 145kW and 150kW units do not
ship with disconnect plugs and must be hard wired to the
main line circuit breaker.

The bag contains an instruction sheet, 2 plug bodies, four
contacts, a handle and the hardware to assembly the
disconnect plug. You will need to purchase the appropriate
length of fine stranded copper wire for your application in order
to complete the assembly of the disconnect plug.

Figure 1

Advertising
This manual is related to the following products: