SPECIFICATIONS

GENERATOR SPECIFICATIONS

RP55

KILOWATT

45 kW

KILOVOLT-AMPS (.8 PF)56 kVA
AMPERAGE

277/480 VOLT 3 PHASE 68 AMPS*
120/240 VOLT 3 PHASE 135 AMPS*
120/208 VOLT 3 PHASE 150 AMPS*
120/240 VOLT 1 PHASE 188 AMPS**

*Based on .8 power factor
**Single Phase is limited by the circuit breaker to 150
Amps on the full power terminal block - The additional
amperage is available through receptacles.

Derate 3% per 1000 feet (305 meters) between 300 feet
(90 meters) and 7,500 feet (2,286 meters) above sea
level. Contact the factory for rating data for operation in
altitudes above 7,500 feet (2,286 meters).

For prime power application (24/7) derate all output rating
by 10%

RP80

KILOWATT

65 kW

KILOVOLT-AMPS (.8 PF)80 kVA
AMPERAGE

277/480 VOLT 3 PHASE 98 AMPS*
120/240 VOLT 3 PHASE 195 AMPS*
120/208 VOLT 3 PHASE 225 AMPS*
120/240 VOLT 1 PHASE 233 AMPS**

*Based on .8 power factor
**Single Phase is limited by the circuit breaker to 225
Amps on the full power terminal block - The additional
amperage is available through receptacles.

Derate 3% per 1000 feet (305 meters) between 300 feet
(90 meters) and 7,500 feet (2,286 meters) above sea
level. Contact the factory for rating data for operation in
altitudes above 7,500 feet (2,286 meters).

For prime power application (24/7) derate all output rating
by 10%

GENERATOR RESISTANCE

RP55

RP80

Generator Make

Stamford

Stamford

Generator Model

UCI224E

UCI224F

Generator Winding

#311

#311

Voltage Regulator

SX460

SX460

Main Stator

0.05 ohms

0.033 ohms

Main Rotor

0.69 ohms

0.83 ohms

Exciter Stator

20 ohms

20 ohms

Exciter Rotor

0.156 ohms

0.156 ohms

ENGINE SPECIFICATIONS

See Iveco Operation and Maintenance Manual for com-
plete engine specifications.

TRAILER/HOUSING

RP55/RP80

Capacity

7000 lb.

Fuel Capacity

110 Gallons

Axles

Single

Hitch Height

Adjustable

Tires

P225/75R-15

Tire Pressure

35 psi

Sound Attenuated

ULTRA QUIET

Housing

Housing Standard

PREPARATION

NOTE: This booklet covers the entire unit, EXCEPT THE
ENGINE. See the engine manufacturer’s operator manual
for specific maintenance and care information regarding
the engine. Read ALL instructions in the manuals pro-
vided before attempting to operate the generator set.

UNPACKING

When receiving the unit, be sure to inspect it carefully for
freight loss or damage. Check the nameplate to be sure it
is what you ordered (proper kW, voltage, fuel, etc.). If you
have questions, contact your local authorized dealer. If
you see evidence of loss or damage at the time of deliv-
ery, have the driver sign and describe the loss or damage
in the “memo of loss or damage” section on the freight
bill. Then contact the carrier to get instructions on filing a
claim.

When loss or damage is discovered after the equipment
is delivered, but not seen at the time of delivery, it is
referred to as “concealed damage.” Separate any dam-
aged material and contact the carrier for proper proce-
dures to file a “concealed damage” claim.

OIL REQUIREMENTS

This engine was filled at the factory. Before starting
check the oil level and ensure it is full. If not, refill to the
proper level. See engine manual for proper grade of oil.

OIL QUANTITY

US Qt.

Liters

RP55

12

12.8

RP80

12

12.8

FUEL REQUIREMENTS

See your engine operator's manual for complete type and
fuel grade information.

WARNING -NO BIODIESEL