SPECIFICATIONS

GENERATOR SPECIFICATIONS

MDS50

KILOWATT

40 kW

KILOVOLT-AMPS (.8 PF)50.0 KVA
AMPERAGE

277/480 VOLT 3 PHASE 60.2 AMPS*
120/240 VOLT 3 PHASE 120.4 AMPS*
120/208 VOLT 3 PHASE 139 AMPS*
120/240 VOLT 1 PHASE 166.7 AMPS

*Based on .8 power factor at 130 degrees C.

Derate 3% per 1000 feet (305 meters) between 300 feet
(90 meters) and 7,500 feet (2,286 meters) above sea
level. Contact the factory for rating data for operation in
altitudes above 7,500 feet (2,286 meters).

GENERATOR RESISTANCE’S

MDS50

Main Stator

.075 ohms

Main Rotor

3.6 ohms

Exciter Stator

25 ohms

Exciter Rotor

.035 ohms

Exciter Voltage (F1-F2)

No Load

9.5 VDC

Full Load

39 VDC

Exciter Amperage (F1-F2)

No Load

.4 Amps

Full Load

1.3 Amps

ENGINE SPECIFICATIONS

See John Deere Operation and Maintenance Manual for
complete engine specifications.

TRAILER/HOUSING

MDS50

Capacity

5000 lb.

Fuel Capacity

80 gals

Axles

Single

Hitch Height

Adjustable

Tires

P225/75-15

Tire Pressure

35 psi

Sound Attenuated

ULTRA QUIET

Housing

Housing Standard

PREPARATION

NOTE: This booklet covers the entire unit, EXCEPT THE
ENGINE. See the engine manufacturer’s operator
manual for specific maintenance and care information
regarding the engine. Read ALL instructions in the
manuals provided before attempting to operate the
generator set.

UNPACKING

When receiving the unit, be sure to inspect it carefully for
freight loss or damage. Check the nameplate to be sure it
is what you ordered (proper kW, voltage, fuel, etc.). If
you have questions, contact your local authorized dealer.
If you see evidence of loss or damage at the time of
delivery, have the driver sign and describe the loss or
damage in the “memo of loss or damage” section on the
freight bill. Then contact the carrier to get instructions on
filing a claim.

When loss or damage is discovered after the equipment
is delivered, but not seen at the time of delivery, it is
referred to as “concealed damage.” Separate any dam-
aged material and contact the carrier for proper proce-
dures to file a “concealed damage” claim.

OIL REQUIREMENTS

This engine was filled at the factory with John Deere
Engine Break-In Oil. This break-in oil should be drained
and the oil filter changed after the first 100 hours of
operation.

During the break-in period, add John Deere Engine
Break-In Oil as needed to maintain the specified oil level.

A second 100-hour service interval with John Deere
Engine Break-In Oil may be required if the engine is
operated under light loads during the first 100 hours.

After the break-in period, use John Deere Torq-Grad
Supreme Plus-50 or other heavy -duty diesel engine oil
as recommended in the John Deere Engine manual. See
your engine operator's manual for recommended oil
grades and types under different operating temperatures.

OIL QUANTITY

US Qt. Liters

MDS50

9.0

8.5

FUEL REQUIREMENTS

See your engine operator's manual for complete type and
grade fuel information.

Filling the Fuel Tank

Standard Trailer - The standard trailer is equipped with a
single 80 gallon fuel tank. Use caution when filling the
tank not to overflow the tank into the trailer.

WARNING PERSONAL DANGER
Never refuel a running engine,. Always stop the engine
and allow to cool before refueling.

Never allow the fuel tank to run completely empty, as air
may enter the fuel system making it necessary to bleed
the engine when restarting.