User Manual

- ONLINE 6K/10K RACK-TOWER ISOTX UPS

ENGLISH

__________________________________________________________________________________________________________________________

www.xmart-ups.com

130717 RT9- 6K-10K (ENG)

- 38

SETTING / OTHERS

Others:

-->

Hot Standby

Backup Time

Hot Standby:

-->

Status: Disable

Backup Time:

-->

Batt Groups: 1

Batt Cap: 9AH

Factor: 1.0


HOT STANDBY:


ENABLE:
It allows UPS to restart after a long AC failure even UPS has

no batteries connected.

DISABLE: It allows UPS to work as standard UPS. It will only restart

when AC recovery is detected if UPS has batteries connected.

BACKUP TIME PARAMETERS:

BATT GROUPS: Set the quantity of battery groups connected from 1 to

6. Default is 1.

BATT CAP: Set the battery capacity in AH. Default is 9AH.


FACTOR:
This factor is used to calculate remaining backup time

displayed on LCD. Default is 1.

F5. ALARMS & ERROR SCREEN

Alarm Info

Fault:

14: Output Short

Warning:

01: Batt Open


In this screen warnings and faults are recorded.

Warning and error messages are described in following tables.