09: Maximum battery discharge time setting

Interface

Setting

Parameter 3:

000~999: Set the maximum discharge time from 0 min to 999 min. UPS will shut down

to protect battery if the discharge time arrives before the battery is under voltage. The
default value is 990 min.
DIS: Disable battery discharge protection and backup time will depend on battery

capacity.

10: Reserved

Interface

Setting

Reserve for future options.

11: Reserved

Interface

Setting

Reserve for future options.

12: Neutral loss detection

Interface

Setting

Parameter 2:

N.L: Indicates neutral loss detection function.

Parameter 3:

DIS: Disable the neutral loss detection function. The UPS will not detect the neutral loss

or not.
ATO: The UPS will automatically detect the neutral is lost or not. If neutral loss is

detected, an alarm will be generated. If the UPS is turned on, it will transfer to battery
mode. When neutral is restored and detected, the alarm will be muted automatically and
the UPS will go back to normal mode automatically.
CHE: The UPS will automatically detect the neutral loss. If neutral loss is detected, an

alarm will be generated. If the UPS is turned on, it will transfer to battery mode. When
neutral is restored, the alarm will NOT be muted automatically and the UPS will NOT go

back to normal mode automatically.
Here, you must mute the alarm and make the UPS go back to normal mode manually.
The operation is: Firstly, enter this menu and press the “Enter” key to make the “CHE”
flash. Secondly, press the “Enter” key again to activate the neutral detection (check). If
neutral is detected, the alarm will be muted and the UPS will go back to normal mode. If
neutral is not detected, the UPS will continue alarming and stay on the latest status until
the neutral is detected well at next manual checking operation.