User manual – XMART Optima 33 30K User Manual

Page 13

Advertising
background image

USER MANUAL

- OPTIMA-33 10K / 20K / 30K

www.xmart-ups.com

130612-OPTIMA-33 10K/20K (ENGLISH) - 11

EXTERNAL BATTERY CABINETS – CONNECTION PROCEDURE

UPS Tower type

WARNING

Make sure EXBATT model to be connected is compatible with UPS model. For OPTIMA-33 models, battery pack voltage is 240Vdc.

Measure and verify DC voltage supplied by battery pack before making connections.


1.- Check all DC breakers are in OFF position

2.- Remove all DC connector covers in UPS and EXBATT cabinets

3.- Using appropriate cable (supplied with the EXBATT) connect UPS with EXBATT 1. In case of more than 1 EXBATT connect EXBATT 1 with
EXBATT 2 and so on until last EXBATT.

4.- Activate DC breakers one by one in EXBATT cabinets to connect EXBATT batteries with internal UPS Main batteries.

Advertising
This manual is related to the following products: