BWF Troubleshooting Chart (contd.)

Caution: Read page 43 before attempting to use this chart.

Pilot

light?

24 volts

between

terminals 5 and

6 on S8670?

See "Intermittent

Ignition System

Troubleshooting

Chart" on next page

24 volts

between NO

terminal on

vacuum switch

and C on

R8285D?

Minimum

vacuum at

switch called for

in Table 9 on

page 42 ?

* Defective

vacuum switch

* Blockage in venting system
* Vent system not installed in

accordance with installation manual
* Excessive silicone on I.D. of vent

system joints
* Blockage, condensate or leakage in

vacuum switch tubing
* Improperly sealed flue collector
* Damaged or missing fan gasket
* Defective fan
* Wind at horizontal vent terminal in

excess of 40 mph

* Rollout switch
open. Replace
switch with exact
replacement,
Crown Part #
960122. Check for

blocked heat

exchanger

Main

burners

light?

N

Do burner,

circulator and

fan shut down at

end of call for

heat?

END

Y

Does boiler shut

down when t'stat

wire is removed from

terminal R on

R8285?

* T'stat or zone valve

wiring calling for heat
* T'stat wires shorted

* Internal boiler wiring

problem, consult

Crown representative

Y

N

N

Y

Do burners shut

down before gauge

temp exceeds

high limit setting

+15F?

* Defective L4080B
* Sensing bulb not bottomed

out in well

N

Y

N

N

N

Y

Y

Continued

from previous

page

Y

N

Y