M-lib3 low impedance bus differential relay – Cooper Lighting Low Impedance Bus Differential Relay M-LIB3 User Manual

Page 10

Advertising
background image

M-LIB3 Low Impedance Bus Differential Relay

10

2.6 Technical Data

q

Standards: IEC 255, 1000, CE

q

Rated Frequency: 50/60 Hz

q

Rated input current: 1 A

q

Current overload: 2 In

q

Transient overload: 100 In

q

Setting ranges:

•

F

n

= 50/60 Hz

•

I

ds

= zone differential current = (0,2-2) In

•

R = Bias per Unit = (0,4 - 1) p.u.

•

I

SV

= Circuit supervision current = (0,1 – 1) In

•

Operating time:

≤

20 ms

•

Stability level:

≥

40 I

n

max.

2.7 CURRENT TRANSFORMER REQUIREMENTS

Current transformer requirements

Minimum knee point voltage: V

K

≥

F . In . R

T

where

F = Accuracy limit factor (20 recommended)

In = Main CT’s rated secondary current

R

T

= Total CT’s secondary loop resistance (see equivalent diagram)

Minimum power:

2

In

R

In

F

V

S

CT

K

−

⋅

≥

RCT = Secondary resistance of main CT
RW = Resistance of connection lead
RP = Primary resistance of auxiliary ratio matching CT
n = IP/IS = Current ratio of auxiliary CT
RS = Secondary resistance of auxiliary ratio matching CT
Rd = Ohmic burden of M-LIB3 : 0.52

Ω

(In=1A)

Advertising