ERROR CODE #5 - INDOOR THERMISTOR FAILURE

REASON: CONTROL BOARD READS TEMPERATURE ABOVE ISCTF OR BELOW -SCTF.
POSSIBLE CAUSES:

1) Thermistor failed or out of calibration (see Note 1).

2) Loose or corroded connection.
3) Faulty control board, Interface board or cable.

Reference Figure 22

Notes:

1) If thermistor Is out of calibration, it may read accurateiy with system off, but may drift from actual

temperatures during operation.

2) For furnace appiications - Remove furnace access panei and tape kili switch so that panel can later be

removed for blower inspection without breaking power.

Reinstall access panel.

3) Adjust thermostat 4°F or more above or below room temperature, depending on mode, to force system

to fuli speed.

A87477