Loosen compressor hold-down bolts, Start the unit, Loosen compressor hold down bolts – Carrier 26H User Manual

Page 16: Installation

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

26H

INSTALLATION

18. LOOSEN COMPRESSOR HOLD-DOWN BOLTS

26H5

Loosen the four compressor hold-down bolts. See

Fig. 16. Check to see that the compressor is float­
ing freely on its mounting springs.

When the machine is to be moved, retighten the hold
down bolts to prevent damage.

26H3

The 26H3 is spring mounted internally. Do not

loosen compressor hold-down bolts.

19. START THE UNIT

Shutoff valves are backseated and the unit is ready

for operation when shipped.

Turn the selector switch located under the hinged
nameplate to the "ON "position and check the opera­
tion. See Fig. 17.

If the unit fails to start^ push the reset button on
the Safety Overflow Switch.

NOTE: The 26H5 unit may cycle several times on

the high pressure cutout during initial start­
up or after a prolonged shut-down. While

such cycling is perfectly normal, it may

COMPRESSOR

SHIPPING POSITION

COMPRESSOR
FLANGE

SPRING

SPRING CUP

UNIT FRAME

DO NOT REMOVE

COTTER PIN

WELD NUT

BOLT TIGHT AGAINST

WELD NUT

OPERATING POSITION

FIG. 16 - COMPRESSOR HOLD-DOWN BOLTS

be reduced by shutting off the unit for about
a half a minute then starting again.

The 26H3 may cycle on overload several

times upon attempting to start after a pro­
longed shutdown.

26H-57PD

16