A caution, A warning, Caution – Carrier 61SW User Manual

Page 7: Warning

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

If a manual disconnect switch is to be mounted on the appliance,
select a location where a drill or fastener will not contact electrical

or gas components.

NOTE:

Use only copper wire between the disconnect switch and

the unit.

Check all electrical connections (both factory and field) for

tightness. Recheck tightness of electrical connections after the unit
has reached operating temperatures.

Step 1—Filling The Boiler

Check to be sure that all connections have been made. Before

atternpting any operations, fill the system with water.

A

CAUTION

I Never light a burner under an empty boiler.___________________ |

1. Close air vents on all radiation units,

2. Open water supply valve on each radiation unit.

3. Close drain cock and air bleed screw on boiler expansion tank.

4. Open valve in line from boiler to expansion tank.

5. Open water inlet valve to boiler and leave open.

6. Starting with lowest radiation unit, open air vent.

7. Working from the lowest to the highest radiation unit, repeat

item 6 until you have vented every radiation unit in the

system.

NOTE:

Systems with an automatic vent on each radiation unit

will not require manual venting.

8. Check temperature/pressure gage. It should read between 10

and 15 psig.

9. Check system piping connections for leaks.

START-UP AND ADJUSTMENTS

NOTE:

Safe lighting and other performance criteria were met

with the gas manifold and control assembly provided with the

boiler when it underwent testing as specified in ANSI Z21.13b-

1991.

Check to be sure that all connections have been made. Before

attempting any operation, fill thé system with water. For steam

boilers, fill to the water line. Never light a burner under an empty
boiler.

CHECK PILOT TO BE SURE THAT ALL CONNECTIONS

HAVE BEEN PROPERLY MADE.

Light the pilot, using the procedure outlined on the lighting

instruction plate attached to the boiler.

A

CAUTION

The boiler is equipped with an intermittent-type ignition

device that functions during each thermostat on cycle. DO

NOT USE MATCH OR OTHER OPEN FLAME TO LIGHT

-

pilot

:

1. If the gas supply line was not purged before connecting the

^^=^boilerrit‘will“be~full'of'aii77'is'it"would'talce^long time to vent

this air through the small pilot port, it is recommended that

pilot supply line be disconnected and be allowed to purge until
the odor of gas is detected. Never purge gas lines into the

combustion chamber. Iinmediately upon detection of gas

odor, reconnect pilot supply tube. Allow 5 minutes to elapse,

then light pilot using the procedure outlined on the lighting

instruction plate attached to the boiler.

2. The pilot flame should be soft blue in color and should be

checked periodically. The flame lies under the carryover ports

■ of burners and merges with the carryover flames. The pilot

flame should not touch the boiler section. If the pilot flame

does not have the appearance as described, it can be adjusted.

a. The gas valve is equipped with an adjustable screw.

Remove capscrew to expose adjustable screw. Turn screw

until flame has desired appearance.

b. Replace capscrew.

A

WARNING

The boiler is equipped with an intermittent ignition device

(IID). Check the safety pilot operation as follows; Attach a

low-voltage test light to the electrical leads of the gas valve at

terminals marked 1 (or TH) and 2 (or TR). With the

thermostat set above room temperature (pilot and main

burners operating), turn OFF the gas supply to burners and
pilot with main shutoff valve. If the test light goes out within

45 sec, the safety pilot is functioning properly. If the light

, does not go out within 60 sec, replace the safety pilot. Place

the boiler in normal operation by following the lighting

instructions on the boiler.

GAS INPUT-DETERMINE THE GAS INPUT

1. Natural gas

a. Turn off all other gas appliances and pilots.

b. Measure time (in sec) for gas meter test dial to complete 1

revolution.

c. Refer to Table 5 for cu ft of gas per hr.

d. Multiply cu ft/hr X heating valve' of gas. Obtain heating

valve of gas from local gas utility.

EXAMPLE: .

Btu heating input = Btu/cu ft x cu ft/hr

Heating value of gas = 1070 Btu/cu ft

Time for 1 revolution of 2-cu ft dial = 72 sec

Gas rate = 100 x 1070 = 107,000 Btuh

e. The measured gas input should not exceed the gas input

shown on the unit rating plate.

f. Observe manifold pressure. It should be adjusted to read

3.5- ±0.3-in. wc. Adjust pressure by using an adjusting

screw in the gas pressure regulator stem. (This screw is

concealed under the regulator sealing cap.) Turn screw

clockwise to increase pressure and counterclockwise to

decrease pressure.___________________________

-Small-changes~ihHnput-can-be-made--by-changing-the-manifold“

pressure as previously described. However, the manifold pressure

should not vary more than 0.3-in. wc from the rated pressure.

A further change in gas rate can be accomplished, if necessary due

to high altitude, by changing the fixed orifice at the burners.

A

CAUTION

I Do not under any circumstances redrill orifices.________________

2. Propane gas models

a. These units are equipped with pressure regulators. The

burner orifices are sized to give rated input at a manifold

pressure of 10-in. wc. Check manifold pressure and, if
necessary, adjust pressure.

3. High altitude ratings are approved for altitudes to 2000 cu ft

for all gases. Ratings for altitudes over 2000 ft are 4 percent

less for each 1000 ft above sea level.

Advertising