Contaminated combustion air, Vent and combustion air piping guidelines, Piping insulation guidelines – Sears 9MPD125L20B1 User Manual

Page 11

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

bustion or the furnace can use air from inside the structure for com­
bustion. The INLET air pipe is optional. If combustion air comes
from inside the structure, adequate make up air MUST be provided

to compensate for oxygen burned. See

Confined Space Installa-

tion'm

the

Combustion and Ventilation Air chapter.

If combus­

tion air is drawn from outside the structure, it MUST be taken from
the same atmospheric pressure zone as the vent pipe.

Contaminated Combustion Air

Installations in certain areas or types of structures will increase the
exposure to chemicals or halogens that may harm the furnace.

The following areas or types of strucfures may contain or have ex­
posure to the substances listed below. The installation must be
evaluated carefully as it may be necessary to provide outside air
for combustion.

Commercial buildings.

Buildings with indoor pools.

Furnaces installed in laundry rooms.

Furnaces installed in hobby or craft rooms.

Furnaces installed near chemical storage areas.

Permanent wave solutions for hair.

Chlorinated waxes and cleaners.

Chlorine based swimming pool chemicals.

Water softening chemicals.

De-icing salts or chemicals.

Carbon tetrachloride.

Flalogen type refrigerants.

Cleaning solvents (such as perchloroethylene).

Printing inks, paint removers, varnishes, etc.

Flydrochloric acid.

Sulfuric Acid.

Solvent cements and glues.

Antistatic fabric softeners for clothes dryers.

Masonry acid washing materials.

Vent and Combustion Air Piping Guidelines

This furnace is approved for venting with Schedule 40 PVC,
CPVC, ABS, Cellular Core pipe fittings and SDR-26 PVC.

NOTE: All PVC, CPVC, ABS, and Cellular Core pipe fittings, sol­

vent cement, primers and procedures MUST conform to American

National Standard Institute and American Society for Testing and
Materials (ANSI/ASTM) standards.

Pipe and Fittings -

ASTM D1785, D2241, D2466, D2661,

D2665, F-891, F-628

PVC Primer and Solvent Cement -

ASTM D2564

Procedure for Cementing Joints -

Ref ASTM D2855

NOTE: All vent piping MUST be installed in compliance with local
codes or ordinances, these instructions, good trade practices, and
codes of country having jurisdiction.

1.

Determine the best routing and termination for the vent pipe

and air inlet pipe by referring to all of the instructions and
guidelines in this Section.

2.

Determine the size required for the vent pipe and air inlet

pipe.

3.

Loosely assemble all venting parts without adhesive (pipe

joint cement) for correct fit before final assembly.

4.

Use of vertical piping is preferred because there will be

some moisture in the flue gases that may condense as it
leaves the vent pipe (See

Special Instruction For Horizontal

Vents).

5.

The vertical vent pipe MUST be supported so that no weight

is allowed to rest on the combustion blower.

6

.

Exhaust vent piping or air inlet piping diameter MUST NOT

be reduced.

7.

All exhaust vent piping from the furnace to termination

MUST slope upwards. A minimum of V

4

" per foot of run is

required to properly return condensate to the furnace drain
system.

8

.

Use DWV type long radius elbows whenever possible, as

they provide for the minimum slope on horizontal runs and
they provide less resistance in the vent system. If DWV el­

bows cannot be used, use two, 45° elbows when possible.
On horizontal runs the elbows can be slightly misaligned to
provide the correct slope.

9.

All horizontal pipe runs MUST be supported at least every

five feet with galvanized strap or other rust resistant materi­
al. NO sags or dips are permitted.

10. All vertical pipe runs MUST be supported every six feet

where accessible.

11. The minimum pipe run length is 2'.

12. The piping can be run in the same chase or adjacent to sup­

ply or vent pipe for water supply or waste plumbing. It can
also be run in the same chase with a vent from another 90-r
furnace.

NOTE: In NO case can the piping be run in a chase where

temperatures can exceed 140° F. or where radiated heat

from adjacent surfaces would exceed 140° F.

13. The vent outlet MUST be installed to terminate in the same

atmospheric pressure zone as the combustion air inlet.

14. The vent system can be Installed In an existing unused

chimney provided that:

• Both the exhaust vent and air intake run the length of the

chimney.

• No other gas fired appliance or fireplace (solid fuel) is

vented into the chimney.

• The top of the chimney MUST be sealed flush or crowned

up to seal against rain or melting snow so ONLY the piping
protrudes.

• The termination clearances shown in Figure 7 & Figure 8

are maintained.

15. Furnace applications with vertical vents requiring vent di­

ameter increaser fittings

must

have increaser fittings

installed in vertical portion of the vent. Condensate will be

trapped in the vent if the vent diameter is increased prior to

having an elbow turned upward. This could cause nuisance

tripping of the pressure switch.

Piping Insulation Guidelines

NOTE: Use closed cell, neoprene insulation or equivalent. If Fiber­
glass or equivalent insulation is used it must have a vapor barrier.
Use Rvalues of 7 up to 10’, R-11 if exposure exceeds 10’. If Fiber­
glass insulation is used, exterior to the structure, the pipe MUST
be boxed in and sealed against moisture.

1.

When the vent or combustion air pipe height above the roof

exceeds 30 ', or if an exterior vertical riser is used on a hori­

zontal vent to get above snow levels, the exterior portion
MUST be insulated.

2.

When combustion air inlet piping is installed above a sus­

pended ceiling, the pipe MUST be insulated with moisture
resistant insulation such as Armaflex or other equivalent

type of insulation.

440

01 1020 04

□3

Advertising