White Rodgers 770-1 User Manual

White-rodgers, Instructions - type 770-1 air switch, Specifications

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

WHITE-RODGERS

- INSTRUCTIONS -

TYPE 770-1

AIR SWITCH

With SPDT Switch Action

(Responds to Positive, Negative,

or Differential Pressure)

The Type 770-1 has a SPDT switch that can be actuated by a positive pressure,

negative pressure, or a differential of pressure. These two features, plus its
field adjustable "operating range", give this control unmatched versatility on a
wide variety of applications, some of which are shown below.

TYPICAL APPLICATIONS

POWER HUMIDIFIERS

Switch permits unit to operate
whenever there is proper air move­
ment.

PROCESS DRYING

Switch monitors negative pressure
to stop conveyor or process, and

provides alarm signal on fan failure.

Ideal for bulk chemicals, food
processing, grain drying.

0

ELECTRONIC AIR CLEANERS

Switch permits power to cleaner
whenever blower of system is oper­
ating.

REFRIGERATION EQUIPMENT

Switch responds to pressure drop
across refrigeration coils to signal
alarm condition or automatically ini­
tiate or terminate defrost cycle.

NATURAL DRAFT BOILERS

Switch signals insufficient draft,

provides safety limit to stop firing
on lack of draft, starts again on
sufficient draft.

GAS-FIRED UNITS

Switch proves sufficient air flow be­
fore permitting gas valve to open
and ignition to occur.

-

0

-

INDUCED DRAFT BOILERS

Proves operation of I.D. fan by
sampling draft or air flow.
Shuts off firing equipment on fan
failure.

DUCT STRIP HEATERS

Switch proves air movement across
heaters by positive pressure in front
of heater. Turns off heater to pre­
vent burn-out on insufficient air
flow.

FORCED DRAFT BOILERS

Proves operation of blower by
sampling positive or negative pres­
sures for firing control and safety.

LEGEND

Negative Pressure

Positive Pressure

Pressure Differential

Pressure Sample Line

-SPECIFICATIONS-

ELECTRICAL RATING

15 AMP 125/250/277 VAC NT.
1/4 HP 125 VAC.
1/2 HP 250 VAC.

ELECTRICAL SWITCH

Single pole, double
throw snap action switch

CONTROL SET POINT

Adjustable

FIELD ADJUSTABLE

On pressure rise at .05
to 12" w.c.

CONDUIT OPENING

7/8" diameter opening
accepts 1/2" conduit

RECOMMENDED OPERATING POSITION

Diaphragm vertical

OPERATING TEMPERATURE RANGE

-40 to 180° F.

SAMPLE LINE CONNECTORS

Male externally threaded 7/16"-24
UNS 2 A thread complete with nut
and self aligning ferrule.

SAMPLE LINE CONNECTIONS

Connectors will accept 1/4" O.D.
rigid or semi rigid tubing. Slip
on tubing adaptors optional.

WHITE-RODGERS DIVISION

EMERSON ELECTRIC CO.
9797 REAVIS ROAD

ST. LOUIS, MISSOURI 63123

IsMIERSaN

®

Printed in U.S.A.

PART No. 37-4898A

Replaces 37-4395

9110

4324

Rev.B