REPLACING "OLD STYLE” FLAME SENSORS (continued)

B. Oil Line-Mounted Flame Sensor (Fig. 6)

1. Observe flame sensor position and mark location of Cad

Cell on the oil line for reference as shown in Fig. 6. Then
remove and discard the entire Flame Sensor by
removing screw holding mounting bracket to the oil line.

2. Assemble new 956-128 Flame Sensor as shown in Fig.

2

.

3. Install new Flame Sensor to oil line taking care to locate

mounting bracket so that Cad Cell of new Flame Sensor

will have same view of the oil flame as the old Flame
Sensor (use reference mark on oil line). Be sure screw is
securely tightened.

4. Reconnect leads of Flame Sensor to primary control,

being sure that leads are clear of blower wheel.

5. Close ignitign transformer, being sure Flame Sensor

leads are clear of cover. Restore electric power and
check burner for proper operation.

C. Flame Sensor Mounted on Side of Burner Housing (Fig. 7)

1. Remove Housing Mounting Clip from side of burner

housing as shown in Fig. 7. Then remove and discard old

Flame Sensor from Housing Mounting Clip.

2. Assemble new 956-133 Flame Sensor as shown in Fig. 3.

3.

Insert bracket of new Flame Sensor into Housing

Mounting Clip. Then replace Housing Mounting Clip on

side of burner housing.

4. Reconnect leads of Flame Sensor to primary control,

being sure that leads are clear of blower wheel.

5. Close ignition transformer, being sure Flame Sensor

leads are clear of cover. Restore electric power and
check burner for proper operation.

OIL LINE

\

■71

OF CAD CELL

CELL -

unn

______P

FLAME SENSOR

Fig. 6 — Old Style Flame Sensor.