Content s – CPG FIRELARM 2500 CPG #2561255 User Manual

Page 18

Advertising
background image

Content

s

1

2

3

CPG #2561255

F

IRE

L

ARM

2500 Operating Manual


3-4

Table 3-1: Current Requirements.

Module/Device

Standby mA

Alarm mA

2500 with LCD display
2500 without LCD display
CAM (Class A module)
RALCD (Remote Annunciator)
ZDACT (Digital Alarm Communicator)
MBM module
PAM-1 or PAM-2 Relay

170
105

0

95
30
30
15

310*

250

25

115

50

15 (250 momentary)

15

*Includes one zone short circuit current.

Table 3-2: Secondary Power Requirements.

NFPA-72 National Fire Alarm Code

Standby Time

Alarm Time


Local Systems
Auxiliary Systems
Remote Station Systems
Central Station Systems

24 hrs.
60 hrs.
60 hrs.
24 hrs.

5 min.
5 min.
5 min.
5 min.

Table 3-3: Calculation Table.

1 2

3

4 5

6

Module/Device

Qty.

Standby mA Per Unit

Total Standby
Current

Alarm mA Per Unit

Total Alarm
Current

Total mA

Total mA

Convert to A

X 0.001 Convert to A

X 0.001

Total A

Total A

Multiply by hours
from table 2

X

AH for 5 mins.

÷ 12

Total Standby AH

Total Alarm AH

+ Total Standby AH

Total

AH

Efficiency Factor

÷ 0.85

Required

AH

 Select a battery such that the battery’s amp hour rating meets or exceeds the

calculated amp hour requirement (44AH maximum).