2.4 Flush Panel-Mounting: CPxF/CPxR 21A

Prior to performing subsequent steps, ensure the panel-mounting location (including
panel thickness) is suitable for the C

Y

RAQ 21, and meets Environmental requirements in

Specifications section.

3

N

OTE

: Panel thickness should not exceed: .55" (14.1mm) Suggested panel thickness

is calculated based on standard C

Y

RAQ 21 parts and dimensions, custom units may not

meet these specifications. Poron

gasket is installed by CyberResearch, Inc. on CPBF &

CPBR 21 models.

2.4.1 Panel Mounting the Monitor

1. Panel cutout is 405mm H x 489mm W for landscape installation (Figure 7).
2. Install the display in panel cut out. Ensure all studs clear cutout opening and

Poron

gasket on the rear of the unit is flush against panel (critical for NEMA

compliance).

3

N

OTE

: Steps 3 & 4 require a second person

3. Align studs on the rear of display with the holes in mounting plate from the rear

of panel (as seen in Figure 7).

Important!

Do not exceed 30 in/lbs when tightening mounting nuts.

4. Also from rear of the panel, second person must install and tighten the fourteen

10-32 mounting nuts.





See Next Page For Illustration