Drolet WOODSTOVES User Manual
Page 12
![background image](/manuals/73056/12/background.png)
CLEARANCES FROM COMBUSTIBLES
It is of outmost importance that the clearances to combustible materials be scrupulously
respected upon installation of the stove you have selected. Refer to the tables below :
Single pipe / Double pipe
Model A
B
C
D
E
F
Eldorado 15/6
18/18
12/12
21.5/12.5 30.5/30.5 24/24
Adirondack 15/5
12/12
10/8
21.5/11.5 24.5/24.5 22/20
Savannah 15/6
18/18
12/12
21.5/12.5 30.5/30.5 24/24
Celtic 15/5
12/12
10/8
21.5/11.5 24.5/24.5 22/20
Jurassien 14/7
8/8
10/6
20.8/13.7 23.5/23.5
22.2/18.2
• Floor to ceiling height must be at least 7' (84") in all cases.
• The clearance between the flue pipe and a wall are valid only for vertical walls and for
vertical flue pipe.
• The flue pipe must not go through roof trussing, an attic, a wardrobe, a floor, a
combustible partition, or similar spaces.
• A flue pipe crossing a combustible wall must have a minimum clearance of 18".
• To reduce flue pipe clearances from combustible materials, contact your local safety
department.
11