If you are considering integrating a Dometic

refreshment center into the furniture, don’t forget that

the cooling unit needs fresh air! These sketches show

various ways to integrate and ventilate a unit.The

open cross-section for fresh air supply and extracted

air must be at least 31 square inches (200 cm

2

), and

the air flow around the cooling unit should be

unrestricted. If you have any questions, Dometic’s

experts will be happy to answer them.

■

Ventilation

11

■

Sufficient ventilation can be accomplished

even in taller furniture. For proper cooling, the

air needs to flow freely around the cooling unit

and exit freely at the top.

■

The opening for supply air can also be built

into the furniture base, but the footprint must

not prevent the air from passing the cooling

unit freely.

■

Should you want to place the unit on the

floor panel of your furniture, be sure to use the

optional 1-5/8” (42 mm) feet.These and an air

grille integrated in the furniture door ensure

sufficient ventilation. Both doors can be

connected with a slide hinge which

compensates for the different pivot points.