Horizontal installation – American Energy Systems MagnuM T40 User Manual
Page 9

HORIZONTAL INSTALLATION
EXHAUST VENT TERMINATION SHALL BE AS FOLLOWS:
A MINIMUM OF 4 FEET/1220 mm BELOW, BESIDE, AND 1 FOOT ABOVE ANY DOOR OR
WINDOW THAT OPENS, OR ANY OPENING INTO A BUILDING.
A MINIMUM OF 2 FEET/610 mm FROM ANY ADJACENT BUILDING OR OVERHANG.
A MINIMUM OF 7 FEET/2130 mm ABOVE GRADE, WHEN LOCATED ADJACENT TO
PUBLIC WALKWAYS.
A MINIMUM OF 2 FEET/610 mm ABOVE GRASS, PLANTS OR OTHER COMBUSTIBLES.
Note: The pipe lengths shown are for reference only.
Your actual pipe length requirements may differ.
SINGLE WALL PIPE SHALL NOT BE
USED FOR ANY INSTALLATION.
HORIZONTAL INSTALLATION SHALL
BE A MAXIMUM OF 5’ FEET.
WARNING:
Vent surfaces can become hot enough to cause burns
if touched. Non-combustible shielding may be required.
PLEASE FOLLOW THE PIPE MANUFACTURER’S INSTRUCTIONS AND LOCAL BUILDING CODES FOR
THE CLEARANCE TO COMBUSTIBLES REQUIRED FOR INSTALLATION OF THE VENT PIPE BEING USED.