4. How to move out a PDU (without a replacement) ?
Step 1
- Prepare an appropriate length Cat. 5/6 cable.
Step 2
- Click Disable Monitoring in <Details> page to stop monitoring the removed PDU.
Step 3
- Use the Cat. 5/6 cable to bridge over the removed PDU to minimize log/data loss.
Step 4
- Power off & unplug the device(s) which connected to the PDU.
Step 5
- Power off & remove the PDU from connection.
Step 6
- Enable alarm email in <Alarm> page.
If the removed PDU NOT in the last level, you MUST reconfi gure and reset the level for
the affected PDU(s) which next to the removed PDU.
Ignore step 1 & 3 if the removed PDU is in the last level.
5. How to add an extra PDU to an existing PDU group ?
Step 1
- Prepare a PDU and set the PDU level accordingly.
(Please refer to < 1.2 > display 9.1 for the PDU level setting )
Step 2
- Prepare an appropriate length Cat. 5/6 cable.
Step 3
- Click Set maintenance in <Details> page for the affected PDU(s) which next to the
added PDU.
Step 4
- Install and connect the new PDU.
Step 5
- Power on the new PDU.
Step 6
- Reconfi gure & reset the level for the affected PDU(s) which next to the added PDU.
Step 7
- Click Remove maintenance in <Details> page for the affected PDU(s).
Step 8
- Click Search in <Status> page to search the new installed PDU.
Step 9
- Confi gure the new PDU in <Details> and <TH Sensor> page such as
Alarm Amp
, Name, Location…
Step 10
- Enable alarm email in <Alarm> page.
Ignore step 3, 6 & 7 if the added PDU is in the last level