Part viii. troubleshooting – Austin Hughes IPM-03 User Manual
Page 53

www.austin-hughes.com
UM-IPM-03-Q214V3
P.48
Replacement, Removal or addition for PDU & IP dongle
4. How to move out a PDU (without a replacement) ?
Step 1 - Prepare an appropriate length Cat. 5/6 cable.
Step 2 - Click Disable Monitoring in <Details> page to stop monitoring the removed PDU.
Step 3 - Use the Cat. 5/6 cable to bridge over the removed PDU to minimize log/data loss.
Step 4 - Power off & unplug the device(s) which connected to the PDU.
Step 5 - Power off & remove the PDU from connection.
Step 6 - Enable alarm email in <Alarm> page.
If the removed PDU NOT in the last level, you MUST reconfi gure and reset the level for
the affected PDU(s) which next to the removed PDU.
Ignore step 1 & 3 if the removed PDU is in the last level.
5. How to add an extra PDU to an existing PDU group ?
Step 1 - Prepare a PDU and set the PDU level accordingly.
(Please refer to user manual < 1.2 > display 9.1 for details )
Step 2 - Prepare an appropriate length Cat. 5/6 cable.
Step 3 - Click Set maintenance in <Details> page for the affected PDU(s) which next to the
added PDU.
Step 4 - Install and connect the new PDU.
Step 5 - Power on the new PDU.
Step 6 - Reconfi gure & reset the level for the affected PDU(s) which next to the added PDU.
Step 7 - Click Remove maintenance in <Details> page for the affected PDU(s).
Step 8 - Click Search in <Status> page to search the new installed PDU.
Step 9 - Confi gure the new PDU in <Details> and <TH Sensor> page such as Alarm Amp , Name,
Location…
Step 10 - Enable alarm email in <Alarm> page.
Ignored step 3, 6 & 7 if the added PDU is in the last level
Part VIII. Troubleshooting