Part viii. troubleshooting – Austin Hughes IPM-03 User Manual

Page 53

Advertising
background image

www.austin-hughes.com

UM-IPM-03-Q214V3

P.48

Replacement, Removal or addition for PDU & IP dongle

4. How to move out a PDU (without a replacement) ?

Step 1 - Prepare an appropriate length Cat. 5/6 cable.

Step 2 - Click Disable Monitoring in <Details> page to stop monitoring the removed PDU.

Step 3 - Use the Cat. 5/6 cable to bridge over the removed PDU to minimize log/data loss.

Step 4 - Power off & unplug the device(s) which connected to the PDU.

Step 5 - Power off & remove the PDU from connection.

Step 6 - Enable alarm email in <Alarm> page.

If the removed PDU NOT in the last level, you MUST reconfi gure and reset the level for

the affected PDU(s) which next to the removed PDU.

Ignore step 1 & 3 if the removed PDU is in the last level.

5. How to add an extra PDU to an existing PDU group ?

Step 1 - Prepare a PDU and set the PDU level accordingly.

(Please refer to user manual < 1.2 > display 9.1 for details )

Step 2 - Prepare an appropriate length Cat. 5/6 cable.

Step 3 - Click Set maintenance in <Details> page for the affected PDU(s) which next to the

added PDU.

Step 4 - Install and connect the new PDU.

Step 5 - Power on the new PDU.

Step 6 - Reconfi gure & reset the level for the affected PDU(s) which next to the added PDU.

Step 7 - Click Remove maintenance in <Details> page for the affected PDU(s).

Step 8 - Click Search in <Status> page to search the new installed PDU.

Step 9 - Confi gure the new PDU in <Details> and <TH Sensor> page such as Alarm Amp , Name,

Location

Step 10 - Enable alarm email in <Alarm> page.

Ignored step 3, 6 & 7 if the added PDU is in the last level

Part VIII. Troubleshooting