Troubleshooting – Danby DDR60B3WP User Manual

Page 16

Advertising
background image

Troubleshooting

Occasionally, a minor problem may arise, and a service call may not be necessary- use this troubleshooting guide for a
possible solution. If the unit continues to operate improperly, call an authorized service depot or Danby’s Toll Free Num-
ber

for assistance.

Tel: 1-800-26 - (1-800-263-2629)

PROBLEM

POSSIBLE CAUSE

SOLUTION

Dehumidifi er does
not start

• The

dehumidifi er is un-

plugged

The fuse is blown/circuit
breaker is tripped

• Dehumidifi er has reached

its preset level or bucket is
full

Bucket is not in the proper
position

• Power

failure

Make sure the plug is pushed completely into the outlet

Check the house fuse/circuit breaker box and replace the
fuse or reset the breaker

The unit turns off automatically when either condition
occurs. Change to a lower setting or empty the bucket and
replace properly

The bucket must be in place and securely seated for the
unit to operate.

There is a protective time delay (up to 3 minutes) to pre-
vent tripping of the compressor overload. For this reason,
the unit may not start normally for 3 minutes after it is
turned back on.

Dehumidifi er does
not dry the air as it
should

Did not allow enough time
to remove the moisture

• Airfl ow is restricted
• Dirty

fi lter

The humidity control may
not be set low enough

Doors and windows may
not be closed tightly

Clothes dryer may be blow-
ing moisture-laden air into
the room

Room temperature is too
low

• When

fi rst installed, allow at least 24 hours to maintain the

desired dryness

Make sure there are no curtains, blinds or furniture block-
ing the front or back of the dehumidifi er. See the “Location”
section.

See the “Air fi lter” section

For drier air, press the button and set to a lower percent
value (%)

Check that all doors, windows and other openings are
securely closed

Install the dehumidifi er away from the dryer. The dryer
should be vented to the outside.

Moisture removal is best at higher room temperatures.
Lower room temperatures will reduce the moisture removal
rate. Modes are designed to be operated at temperatures
above 5°C (41°F)

Dehumidifi er runs
too much

Area to be dehumidifi ed is
too large

Doors and windows are
open

The capacity of your dehumidifi er may not be adequate

Close all doors and windows

Frost appears on
the coils

Unit has been recently
turned on, or room tempera-
ture is below 5°C (41°F)

This is normal. Frost will usually disappear within 60 min-
utes. See the “Defrost” section

Controls cannot be
set

The compressor will turn
off and the fan will auto-
matically continue to run for
approx. 3 minutes at a fi xed
setting

This is normal. Wait approximately 3 minutes and set the
fan as desired.

Fan noise

Air is moving through the
dehumidifi er

This is normal

Water on fl oor

Hose connection may be
loose

Bucket used to collect wa-
ter, but the hose is attached

Check the hose connection. See “Continuous Drain” sec-
tion

Disconnect the hose if using the bucket to collect water,
see “Continuous Drain” section.

12

Advertising