Dunkirk WPSB Series II User Manual

Page 7

Advertising
background image

7

CONNECTING SUPPLY AND RETURN PIPING

RELIEF VALVE

DISCHARGE

LINE

Check local

codes for

maximum

distance

from fl oor

or allowable

safe point of

discharge

.

WARNING

Burn or Scald Hazard. Discharge line shall be installed to relief valve outlet connection to avoid burns,

scalding, or water damage due to discharge of steam and/or hot water during operation.
Discharge line shall:

• Connect to relief valve outlet and piped down to safe point of disposal. Check local codes for maximum

distance from fl oor or allowable safe point of discharge.

• Be of pipe size equal to or greater than that of the relief valve outlet over the entire length of discharge

line.

• Have no intervening shutoff valve between safety relief valve and discharge to atmosphere (do not plug

or place any obstruction in discharge line.

• Terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing.
• Allow complete drainage of the valve and the discharge line.
• Be independently supported and securely anchored to avoid applied stress on the relief valve.
• Be as short and straight as possible.
• Terminate with plain end (not threaded).
• Be constructed of material suitable for exposure to temperatures of 375°F (191°C); or greater.

Refer to local codes and appropriate ASME Boiler and Pressure Vessel Code for additional installation

requirements.

!

Figure 1 - Safety Relief Valve