Dunkirk Excelsior EXB Series User Manual

Page 44

Advertising
background image

44

6.

Genisys Control Sequence of Operation

A. Standby. Burner is idle, waiting for call for heat.
B. Valve-On Delay. Igniter and motor are on while

control delays turning on oil solenoid valve for pro-

grammed time.

C. Trial for Ignition. Oil solenoid valve is energized.

Flame should be established within factory set trial for

ignition time (“lockout time”).

D. Lockout. Control has shut down for one of following

safety reasons:

I. Trial for ignition (lockout) time expired without flame

being established.

II. Cad cell detected flame at end of Valve On Delay

State.
To reset from hard lockout, hold reset button 15

seconds until yellow light turns on.

E. Ignition Carry-over. Once flame is established,

igniter remains on for 10 additional seconds to ensure

flame stability.

F. Run. Flame is sustained until call for heat is satisfied.

Burner is then sent to Motor-Off Delay, if applicable, or

it is shut down and sent to Standby.

G. Recycle. If flame is lost while burner is firing, control

shuts down burner, enters 60 second recycle delay,

and repeats ignition sequence. Control will continue to

recycle each time flame is lost, until it reaches preset

time allotment. Control will then go into Hard Lockout

instead of recycle. Feature prevents excessive accu-

mulation of oil in the boiler firing chamber.

H. Motor-Off Delay. If applicable, oil solenoid valve is

turned off and control delays turning motor off for set

motor-off delay time before control returns to standby.

I. Pump Prime. Igniter and motor are on with solenoid

valve energized for 4 minutes. During Pump Prime

mode, cad cell is disregarded, allowing technician to

prime pump without having to jumper cad cell.

7.

Genisys Control Reset Button Operation

See Table 11 for action control takes when reset button is

pressed for different lengths of time during various burner

operation states.

16 - OPERATING THE BOILER - SYSTEM START-UP

Figure 38 - Sequence of Operation

Table 11 - Genisys Control Reset Button Operation

If burner is in below

state:

Pushing reset button will:

Button Click

(press < 1 second)

Button Hold

(press > 1 second)

Button Hold

(press 15+ seconds)

Lockout

Reset from Soft Lockout

Reset from Restricted (Hard)

Lockout

Valve-on Delay, Trial for

Ignition, Ignition Carry-

over

Go to Pump Prime

See

“Priming the Pump” page 44

Disable Burner: Anytime

burner is running, press and

hold reset button to disable

burner. Burner will remain off

as long as button is held.

Enables Pump Priming: After

reset button has been held for

15 seconds, button can then

be clicked during next ignition

sequence to enter Pump

Prime mode.

Run (Igniter shut off)

No Action

Motor-Off Delay, Standby

No Action

Pump Prime

No Action

Exit Pump Prime mode and return to Standby

Table 12 - Genisys Control Status Lights

Light Color On Continuously

Flashing

Red

Restricted (Hard) Lockout

Soft Lockout

Green

Flame Sensed during normal operation

(Possible stray light during standby)

Recycle

Yellow

Control is in Pump Prime mode or

reset button currently held for 15+ seconds.

N/A