A MAJOR CAUSE OF CHIMNEY

RELATED FIRES IS FAILURE TO

MAINTAIN REQUIRED CLEARANCES

(AIR SPACES) TO COMBUSTIBLE

MATERIALS. IT IS OF THE UTMOST

IMPORTANCE THAT THIS CHIMNEY

BE INSTALLED ONLY IN

ACCORDANCE WITH THESE

INSTRUCTIONS.
APPLICATION AND LISTING

A DuraTech Adjustable Length is a listed com-

ponent of the UL Listed DuraTech Chimney

System (MH7399). Installation of the Adjust-

able Length must comply with both these

supplementary installation instructions and the

full DuraTech Chimney Installation Instructions

(L150).
INSTALLATION NOTES

Practice good workmanship. Exercise extreme

caution when working on roofs. Be sure to

wear appropriate safety gear and clothing

as needed. You must useonly authorized

DuraTech Chimney parts to maintain a listed

Chimney system (not including the connector

pipe). Do not mix parts or try to match with

other products, or use improvised solutions.

Do not install damaged or modified parts.

Refer to the full DuraTech Chimney Installation

Instructions for further safety details.
WARNING

DuraTech Chimney system is listed with a

2” minimum clearance (air space) to com-

bustibles. Always maintain a minimum of 2”

clearance between chimney pipe and nearby

combustibles. Failure to maintain the minimum

2” clearance to combustibles can result in a

fire hazard.
INSTALLATION

The DuraTech Adjustable Length is used

when an exact length of chimney is needed

and standard lengths of chimney are not

sufficient. The Adjustable Length spans from

minimum of 14” to a maximum of 22” and can

be used between any other DuraTech chimney

sections (straight pipe lengths, elbows, tees,

etc.). The Adjustable Length is a telescoping

section of chimney with both male and female

sections (Figure 1). Within the male section

there are 2” wide strips of insulation that can

be removed to allow for a customized length

(Figure 2).

Figure 1

Figure 2

2” WIDE

INSULATION

STRIPS

14” - 22”

MALE END

SECTION

IF NEEDED, ADJUST

LENGTH BY REMOVING

STRIPS OF INSULATION

(SEE TABLE 1).

MIN 2”

OVERLAP

FEMALE END

SECTION