ENMET MX-42A User Manual

Page 20

Advertising
background image

ENMET Corporation

MX42A C

ONTROL

16

7.5 Alarm

Visual alarms provided: for each channel

•

fault signal lamp:

channel in service: green color

channel off or malfunction of microprocessor: off

disturbance on line: steady yellow color

calibration/adjustment mode: blinking yellow color

•

alarm 1 signal lamp: red color when in alarm

•

alarm 2 signal lamp: red color when in alarm

•

alarm 3 signal lamp: red color when in alarm

Alarms 1 and 2

•

activation after 5 seconds

•

by increasing or decreasing value

•

manual or automatic clearance

Alarm 3

•

activation after elapsed delay time or on basis of average value

•

automatic clearance

•

by increasing or decreasing value

Disturbance

•

complete check of short circuit or cut out of at least one wire (with just one detector)

•

display per channel with yellow signal lamp

Buzzer

Triggered if:

microprocessor malfunction

anomaly of connecting cable or sensor/transmitter

alarm threshold level exceeded

maintenance time longer than 30 minutes