0 installation, 2 mounting, 3 wiring – ENMET CD-1300-ST User Manual
Page 5

CO
2
Sensor / Transmitter
ENMET Corporation
3
3.0 Installation
Figure 1: CD-1300-ST Series, Mounting Dimensions
3.1 Removal of Cover
To open the
CD-1300-ST
series use a coin in the slot on the bottom to release the snap. Lift the cover up slightly to disengage
the closure and remove cover with a downward motion to clear the catch at the top of the unit. The locations of controls and
terminals on the main circuit board are shown in the Figure 2.
3.2 Mounting
The
CD-1300-ST
series is designed for flush mounting with two fasteners. The locations of the mounting points (shown in
Figure 1) allow direct mounting on a standard simplex (single circuit) junction box. There is a wiring cutout in the center of the
unit near the terminal strips.
3.3 Wiring
This section describes the external connections to the CD-1300-ST Series. Wiring enters the chassis through the cutout in the
center of the unit.
Figure 2: CD-1300-ST Series Component Location
3.200
″
2103
″
.
1.600
″
1.103
″
0.000
″
0
.0
0
0
″
0
.4
0
6
″
2
.0
0
3
″
2
.7
5
3
″
3
.5
6
2
″
5
.2
0
0
″
C
USTOMER
W
IRING
N
OTE
:
When connecting to
ENMET
CP-10, CP-60,
LC-8 or other 3-wire type controllers:
1.)
Preferred wiring for long runs,
use 4-wire cable, connect +24VDC, Power
Ground, Signal Ground & 4-20mA at
transmitter and Connect both Power
Ground & Signal Ground together to
ground at the Controller.
2.)
Alternative wiring for short runs,
use 3-wire cable and jumper Power Ground
and Signal Ground together inside the
transmitter.
Sensor
UP
SW1
SW3
SW2
DN
M
JP5
JP4
JP3
JP2
JP1
J5
J5
U3
Microprocessor
Upper Mounting
Screw Access
Wiring Access
+ 24VDC
Power Ground
Lower Mounting
Screw Access
Relay Contact
Signal Ground
4-20mA
Jumper Here for
Current O
UTPUT
Jumper Here for
Voltage O
UTPUT
Option Button
Down Button
Up Button
User Jumpers