14 Replacement of Parts

Diagram 14.11

Diagram 14.12

PUMP HEAD

CAP HEAD
SCREW (4)

14.15 Safety Discharge Valve

For access, refer to section 14.1.

Refer to section 12.8 and drain the boiler heating circuit.

Refer to diagram 14.12.

Undo the safety discharge valve union and remove from the
pipework.

Remove the securing clip and withdraw the safety discharge
valve.

Refill, vent and pressurise the boiler.

Check for leaks.

14.16 Heating Flow Thermistor

For access, refer to section 14.1.

Refer to diagram 14.13.

Remove the electrical connections from the thermistor.

Remove the retaining clip from the flow pipe.

Remove the thermistor from the retaining clip.

Note that the polarity of the wiring to thermistors is unimportant.

14.17 Heating Return Thermistor

For access, refer to section 14.1.

Refer to diagram 14.15.

Remove the electrical connections from the thermistor.

Remove the retaining clip from the return pipe.

Remove the thermistor from the retaining clip.

Note that the polarity of the wiring to thermistor is unimportant.

14.18 Overheat Thermostat

For access, refer to section 14.1.

Refer to diagram 14.13.

Remove the electrical connections from the overheat stat.

Remove the retaining clip from the return pipe.

Remove the overheat stat from the retaining clip.

Ensure that the replacement thermostat is correctly located on
the flat on the return pipe and carefully push the thermistor clip
into place.

OUTLET
CONNECTOR

CABLE
COVER

11507

SAFETY
DISCHARGE
VALVE

11694

Diagram 14.13

RETURN
PIPE

FLOW
PIPE

RETURN
THERMISTOR

OVERHEAT
THERMOSTAT

FLOW
THERMISTOR

11503

RESET
SWITCH