Kipp&Zonen LAS MkII ET system User Manual

Instruction manual, Las mkii et system

Advertising
background image

.

When the system is working properly, roll up extra lengths of signal and power cables and fix them to the mast behind the data
logger enclosure using cable ties.

Do not lay cables on the ground as insects and animals might damage them.

2.10 Installing the scintillometer

Install, configure and optically align the LAS MkII scintillometer using the display and menu keys, or the EVATION software, as
described in the LAS MkII Manual.

When the scintillometer is working properly, switch off the power. Ensure that the power to the data logger enclosure

is turned off.

Connect the receiver analogue outputs for Log

U

C

n

2

and

U

DEMOD

to the data logger OVP inputs, as in the previous table.

Switch on the power to the scintillometer transmitter and receiver and to the data logger enclosure and verify that the
scintillometer signals are displayed and recorded correctly.

Note

As the final step we recommend filling in the Installation Form for the System (see Appendix A). The information

in this form will be used to configure the EVATION software.

Power terminals (low voltage DC only)

Power terminals (mains AC power)

Check that everything is properly fixed to the mast and that the net radiation sensor is level.

Read the relevant sections of the COMBILOG data logger manual.

Note

The COMBILOG data logger in the ET System is pre-configured by Kipp & Zonen and will automatically start

measuring once connected to a power supply.

Switch on the power to the data logger enclosure and verify that all the sensors are working properly. Adjust the date and time
setting of the COMBILOG data logger if necessary.

At this stage do not turn on the power to the LAS MkII scintillometer.

Analogue input channels

2.4 Assembling the meteorological mast and sensors

2.4.1 The mast

Assemble the mast horizontally on the ground in accordance with the dimensions shown below.

The safe clamping zone of each section is indicated by red stripes on each mast section, as shown below.

1. The nominal mast height of 4 m is achieved when clamping the sections at their lower marks.
2. The guy wires are supplied pre-assembled to triangular collar. This must be slid over the upper section of the mast, as shown

above, before fitting any other items.

3. The base plate has a socket for the bottom of the lowest mast section.

LAS MkII ET System

Instruction Manual

.

Please follow the instructions in this section carefully for the mechanical and electrical installation of the LAS MkII ET System.

Do not turn on power to the transmitter or receiver until instructed to do so.

Ensure that fixings and mountings are securely tightened when instructed to do so.

2.1 Included with the system

Check the contents of the shipment for completeness (see below) and note whether any damage has occurred during transport. If
there is damage, a claim should be filed with the carrier immediately. In the case of damage and/or the contents are incomplete,
contact your local Kipp & Zonen representative or e-mail the Kipp & Zonen customer and product support department at:
[email protected]

Note

The LAS MkII is rugged, but it contains sensitive optical and electronic parts. Please keep the original packaging

to safely transport the scintillometer to measurement sites or for other shipments.

2.1.1 LAS MkII scintillometer

The following items are included with the LAS MkII scintillometer:

LAS MkII transmitter with pan and tilt adjuster and baseplate
LAS MkII receiver with pan and tilt adjuster and baseplate
2 × alignment telescope with detachable mounting, adjusted for each transmitter and receiver
2 × sun shield with two fixing screws
2 × 100 mm diameter aperture restrictor with fixing kit, for transmitter and receiver
2 × 10 m cable with 4-pin plug for transmitter signal output and receiver analogue connections
1 x 10 m cable with 8-pin plug for receiver digital communication connections
2 x 10 m cable with 4-pin connector for 12 VDC power input
2 x 3 mm hexagonal Allen keys, for fitting the sun shields
2 x 4 mm hexagonal Allen keys, for fitting the telescopes
1 x CD-ROM containing EVATION software and a pdf file of the LAS MkII instruction manual
8 x spare desiccant packs

For a full description of the LAS MkII scintillometer refer to its instruction manual.

.

2.1.2 Meteorological sensors and mast

The following items are included with the meteorological sensors and mast:

.

2.1.3 NR Lite2 Net Radiometer

The mast includes a mounting arm for the Kipp & Zonen NR Lite2 net radiometer.

2.1.4 COMBILOG Data Logger

The data logger is fitted in a stainless steel weather-proof enclosure with a clamp for the mast.

2.1.5 Additional items

The data logger is fitted in a stainless steel weather-proof enclosure with a clamp for the mast.

• LAS MkII manual, EVATION software and manual (supplied on CD-ROM with the LAS MkII scintillometer)
• Documentation for the meteorological sensors
• COMBILOG support software (supplied on CD-ROM) and manual
• NR Lite2 instruction sheet and calibration certificate (supplied with the NR Lite2)

Note

Kipp & Zonen reserves the right to make changes to specifications without prior notice.

Note

The ET system is not supplied with a relative humidity sensor. A default value (50 %) is used in the EVATION

software. Uncertainties in RH have little effect on the sensible heat flux and the evapo-transpiration.

2.2 Site selection procedure

This section provides information on selecting an appropriate installation site.

2.2.1 LAS MkII scintillometer

For the general installation and site requirements of the LAS MkII scintillometer please refer to its manual.

For reliable air (C

n

2

) and flux (H and L

v

E

) measurements it is important to meet the installation requirements of the scintillometer.

These are:

• The LAS MkII transmitter and receiver must be placed on robust and vibration free supports.
• Avoid saturation of the signal by installing the LAS MkII at a suitable height (depending upon surface conditions and path length).
• Ensure that the LAS MkII is measuring in the Constant Flux Layer for reliable flux derivations of the C

n

2

signal using MOST

(depends on surface characteristics).

Pay attention to orientation, installation height and beam height requirements. For detailed information refer to

the LAS MkII instruction manual.

2.2.2 The meteorological sensors and mast

The LAS MkII receiver is supplied with a 10 m long cable for connecting the two 0 to 2 V analogue signal outputs to the data
logger. Normally, the weather station is sited within 10 m of the receiver, but, if necessary, these cables can be extended to
optimise the weather station location.

Selecting an appropriate site for the weather station is critical in order to obtain data that is representative of the LAS beam
path. It must be sited away from the influence of obstructions such as buildings, trees and other objects which might disturb the
measurements of wind speed, temperature and net radiation. As a rule of thumb, the minimum distance from an obstruction of
height h is 10h.

The ground around the mast should be flat. As the anchoring of the mast is based on 3 securing pins to hold the

guy wires, the soil must be stable enough to hold the load in high winds or when the ground is wet. If in doubt,

use a concrete foundation.

There must be a good, firm place to drive in the lightning rod earth spike.

2.3 Power supply

The LAS MkII transmitter requires 12 VDC nominal (9.6 to 18 VDC), 6 W maximum with heater off and 54 W maximum with heater
on (typically 26 W).

The LAS MkII receiver requires 12 VDC nominal (9.6 to 18 VDC), 5 W maximum with heater off and 51 W maximum with heater
on (typically 23 W).

For more information, please read the LAS MkII scintillometer manual.

The meteorological sensors and data logger require 12 VDC nominal, a total of 4 W maximum with heaters off and 18 W maximum
with heaters on.

Note

The data logger power requirement will be higher if an optional communication modem is fitted. Please refer to

the data logger and/or modem manual.

Mains AC power must be available for AC to 12 VDC convertors, if solar panel / battery power supplies are not used.

.

2.4.2 The mounting arms and sensors

Assemble the mounting arms and sensors to the mast as in the image below.

1. The U-shaped mounting arm is fitted to the top of the mast.
The wind direction sensor (WD) is mounted on the lower (shorter) ‘leg’ of the arm.
The wind speed sensor (u) and lightning rod are mounted on the upper (longer) ‘leg’.

2. The 2-sided mounting arm is fitted to the middle section of the mast at about 2.7 m.
The upper temperature sensor (T+) is mounted on the longer side of the arm.
The NR Lite2 net radiometer (Q* or R

n

)

is mounted on the shorter side of the arm.

The bubble level and the anti-bird stick must be facing upwards.
The net radiometer must be pointing towards the equator to avoid shadows from the mast.

3. The 1-sided mounting arm is fitted to the lower section of the mast at a height of about 0.5 m.
The lower temperature sensor (T-) is mounted on the arm.
The sensor must be oriented vertically below the upper temperature sensor.

When the temperature sensors are positioned too close to each other no reliable direction for the temperature

gradient can be measured, particularly during the day. The minimum distance between the sensors is 1.7 m.

The lower temperature sensor should not be mounted more than 1m above the ground (or the effective surface

height, such as the mean level of grass or a crop around the mast).

4. Use cable ties to fix the sensor cables to the mast and mounting arms and lead the cables to the lower end of the mast, where
at a later stage the data logger enclosure will be mounted.

2.5 Installing the mast

Two persons are required to erect the mast. One person holds the mast in an upright position whilst the second person determines
the positions where the guy wire securing pins will be driven into the ground.

1. The lower guy ends are 0.3 m longer than theoretically required in order to hold the mast vertical on an uneven surface. Two
guy wire ends have a plain thimble, while the third has a bottle screw for adjustment after erection of the mast.

The 3 guy rope securing pins should be driven in at an angle about 20 ° outwards from vertical, as shown below

and in 2.4.1.

2. The securing pin for the guy wire with the bottle screw should be driven in last. First set the bottle screw to its maximum
length. Locate the securing pin so that the mast leans slightly away from it. Use the bottle screw and a spirit level to make
the mast vertical.

The 3 guy ropes should have moderate and equal tension, do not put a bending force on the mast.

.

3. Fix down the base plate of the mast with 4 smaller securing pins.

4. Finally, drive in the lightning rod earth spike

Check the guy wire tension and the mast alignment frequently. If the ground is not firm enough to keep the mast

vertical in all weather conditions, use concrete for anchoring.

2.6 Mounting the data logger enclosure

Once the mast, with mounting arms and sensors, is erected and levelled the stainless steel data logger enclosure can be fixed to
the lower section of the mast, as shown in the next two drawings. Use the two clamps already fitted to the back of the enclosure.
Allow at least 0.1 m clearance below the enclosure for the cables to enter.

.

The installation should now be as in the drawings above.

Note

Check that the net radiometer is horizontal using the bubble level on its upper surface.

2.7 The soil heat flux sensors

The last sensors to be installed are the soil heat flux plates. Place them on the same side of the mast as the net radiation sensor
(towards the equator) and at a spot that is not disturbed by footsteps. The measurements should be representative of the
general area covered.

Do not position the plates directly beneath the net radiation sensor, as they may disturb the measurements.


Depending on the soil type and the presence of vegetation the plates should be buried at a depth of about 30 mm for bare soil
conditions or just beneath the surface of fully covered soil (a few mm). In the latter case the amount of ‘missing’ flux is as small
as possible. Both plates should be at the same depth and laterally separated by 30 to 100 mm.

Do not bury the plates too deeply. At depths of 100 mm they can underestimate the soil heat flux by more than 50 %. Ensure that
the plates are not measuring in air gaps or cracks. They must be in full contact with the soil and at the same depth.

2.8 Sensor overview

2.9 Connecting the sensors

Note

The air pressure sensor (P) is pre-installed inside the data logger enclosure.

All cables (signal and power) enter the data logger enclosure at the bottom through weatherproof cable glands and connect to
the over-voltage protection (OVP) module terminals as in the following table.

Digital input channels

Advertising