MK Plastics Axijet IO&M User Manual
Axijet, Installation, operation, and maintenance manual, High plume exhaust
Fig. 1 – Fan Lifting Lug Details
Handling
Lift the fan by the base or lifting lugs. Never lift by the shaft, motor, housing or wind band.
See Fig. 1 – Fan Lifting Lug Details.
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Bulletin: 77-03-NOVEMBER 2007
Receiving and Inspection
Carefully inspect the fan and accessories for any damage and shortage immediately upon receipt of the fan.
•
Turn the wheel by hand to ensure it turns freely and does not bind.
•
Inspect the dampers (if supplied) for free operation of all moving parts.
This publication contains the installation, operation and maintenance instructions for standard units of the
AXIJET – High Plume Exhaust Systems:
•
Steel Axijets, model Axijet-S size 1825 through 7300
•
FRP Axijets, model Axijet-F size 1225 through 4900
MK Plastics catalog on AXIJET® High Plume Exhaust Systems provides additional information describing the
equipment, fan performance, available accessories, and specifications.
For additional safety information, refer to AMCA publication 410-96, Safety Practices for Users and Installers of In-
dustrial and Commercial Fans.
Page1
AXIJET®
High Plume Exhaust
WARNING
This unit has rotating parts. Safety precautions
should be exercised at all times during installation,
operation, and maintenance.
ALWAYS disconnect power prior to working on
fan.