OPTI-UPS IS5000LR User Manual

Page 28

Advertising
background image

27

Regulation (Nominal)

±5% typical of nominal voltage (optional at ±8% AVR for wide I/P up to ±35%)

Regulation

(Battery mode)

±3% of selected output voltage (adjustable with the remote set-up software)

Transfer time (Typical)

Blackout 3ms; Brownout 1ms; Battery mode to Normal mode 1ms typical

Over current protection Over load alarm level 100% ~ 120%; Over load shutdown level 120% ~ 190%

(Adjustable by using the remote set-up software)

Input

120V Models

230V Models

Nominal Voltage

100V/110V/120V Selectable

220V/230V/240V Selectable

Input Frequency

47Hz ~ 65Hz, 50/60Hz auto-sensing

Efficiency

97% (Normal mode)

Noise Filtering

Full time EMI/RFI filtering

Over current protection

By re-settable over current protector

Voltage Range

-20% ~ +22% for selected nominal voltage.

-29% ~ +33% adjustable by using the remote set-up software

AVR Range

(2 Bucks, 2 Boosts)

Enhanced Buck: +15% of selected nominal voltage

Buck mode: +5% of selected nominal voltage

Boost mode: -5% of selected nominal voltage

Enhanced Boost: -12.5% of selected nominal voltage

Surge Protection

IS2000LR / IS2700LR : 440 Joules

IS4000LR / IS5000LR : 660 Joules

Battery

Battery type

Lead-Acid 25Ah

250Ah

Voltage

IS2000LR / IS2700LR : 48Vdc (24Vdc optional)

IS4000LR : 48Vdc (72Vdc optional)

IS5000LR : 48Vdc

Typical backup time

No Limit

Charging method

Smart pulse charging with two charging modes.

Quick charging when battery is not fully charged, trickle charging when battery

is 90% fully charged.

Average charging

current

11A for IS2000LR / IS2700LR / IS4000LR

20A for IS5000LR(48Vdc)

20A Optional for IS2000LR / IS2700LR / IS4000LR(Below 48Vdc)

P.S. At normal line and normal temperature (Average)