REFCO DIGIMON User Manual
Page 4

HVAC/R
Service Products
Setting Temperature units
Hold the ENTER button and press the R- button to select the desired tempera-
ture unit °F/ °C.
Note: Selected settings will be stored in memory until the next manual change
is made.
Back Light
Press the LIGHT button and the back light will switch on for approximately 30
seconds.
Auto Shut-Off
Approximately 10 minutes after the last measurement or key press the
DIGIMON shuts off itself.
SUPERHEAT/SUBCOOL
Chosen refrigerant and the measured temperature of the external K-type ther-
mocouple (6) or the clamp thermocouple K- type (7).
Changing Superheat/Subcool
Hold the ENTER button and press the
SUPERHEAT/SUBCOOL
to switch bet-
ween superheat and subcool.
Vacuum mode
Press the VAC button to display vacuum mode. Press the VAC button again to
quit this function.
Reading the Vacuum display:
The level of vacuum is shown on the display with (5) five vacuum bars. During
evacuation, the vacuum bars will increase from (1) one bar, no vacuum, to a
maximum of (5) five bars, high vacuum. The more bars displayed, the higher
the vacuum. For a more detailed vacuum level see vacuum specifications.
Note: The DIGIMON must be powered ON before connecting the hoses and
switching on the vacuum pump. If this is not in the correct order the vacuum
display will not show the correct vacuum level.
Note: The DIGIMON must stay powered ON while pulling a vacuum. If the DI-
GIMON is powered OFF while pulling a vacuum, the vacuum display will not
show the correct vacuum level.
The end-vacuum depends on the capacity of the vacuum pump and the current
atmospheric pressure.
For an exact level of vacuum and for vacuum leak checking it is recommended
to use a separate micron vacuum gauge like the VG-64 or the Absolute-Vacuum
Gauge 19621(see REFCO catalog).
Reset
For best results it is recommended to reset/zero the manifold periodically every
40 to 50 hours.
1. Disconnect any hoses.
2. Open low side (blue) and high side (red) valves.
3. Turn on the manifold by pressing the ON / OFF button for 1 second.
4. Press and hold ENTER and LIGHT button at the same time.
5. When the word “ZEro” is shown on the display release ENTER and LIGHT
buttons.