English Instruction Manual DIGIMON-SE / DIGIMON4

12

Connecting the manifold

a) with DIGIMON-SE

Connect blue hose (1)

to suction pressure side of system

Connect red hose (2)

to high pressure side of system

Connect yellow hose (3)

to vacuum pump

Close both valves (5+6)

b) with DIGIMON4

Connect blue hose (1)

to suction pressure side of system

Connect red hose (2)

to high pressure side of system

Connect yellow hose 3/8“ (3)

to vacuum pump

Connect yellow hose 1/4“ (4)

to refrigerant cylinder

Close both valves (5+6)

Evacuating the system

Switch on the manifold

Press the

button

Connect the hoses

Switch on vacuum pump

Open all valves

Check vacuum display

When the ultimate vacuum is achieved, close all valves.

Press the

button to exit vacuum mode.

Evacuation time varies depending on the size of the system. A small to

medium-sized system requires a minimum evacuation time of 20 minutes.

LP/HP

VAC